Siemens SIMATIC ET 200SP Equipment Manual - Page 18

Browse online or download pdf Equipment Manual for Industrial Equipment Siemens SIMATIC ET 200SP. Siemens SIMATIC ET 200SP 44 pages. Distributed i/o system
Also for Siemens SIMATIC ET 200SP: Manual (40 pages), User Manual (21 pages), Manual (34 pages), Manual (48 pages), Manual (30 pages), Manual (34 pages), Product Information (38 pages), Manual (37 pages), Manual (36 pages), Manual (44 pages), Manual (31 pages), Manual (35 pages), Manual (23 pages), Configuration Manual (20 pages), Manual (34 pages), Manual (29 pages), Manual (33 pages), Manual (31 pages), User Manual (32 pages), Manual (31 pages), Manual (28 pages), Manual (41 pages), Manual (32 pages), Manual (49 pages), Manual (24 pages), Manual (34 pages), Manual (41 pages), Manual (30 pages), Manual (31 pages), Manual (27 pages), Manual (24 pages), Manual (24 pages), Manual (25 pages), Manual (49 pages), Manual (40 pages), Manual (38 pages), Manual (39 pages), Product Information (24 pages), Manual (32 pages), Product Information (10 pages), Equipment Manual (43 pages), Manual (33 pages), Original Operating Instructions (6 pages), Manual (35 pages), Manual (28 pages), Equipment Manual (32 pages), Manual (50 pages), Manual (30 pages), Manual (26 pages), Manual (28 pages), Manual (34 pages), Manual (44 pages), Manual (33 pages), Equipment Manual (42 pages), Original Instructions Manual (16 pages)

Siemens SIMATIC ET 200SP Equipment Manual
Product overview
2.3 Properties of the interfaces
2.3.2

Properties of the RS422/485 interface

Definition
The RS422/485 (X27) interface is a differential voltage interface for serial data transmission.
Properties
The RS422/485 (X27) interface has the following properties and meets the following
requirements:
Type
BaseUnit terminals
RS422 signals
RS485 signals
Max. data transmission
rate
Max. cable length
Standard
18
Differential voltage interface
Terminals connected to the electronics module (see RS422/485 interface of
the communications module (Page 23) for assignment)
T (A), R (A), T (B), R (B), GND;
all signals are isolated against the backplane bus and the load voltage
R/T (A), R/T (B), GND;
all signals isolated against backplane bus and load voltage
250 kbps
1200 m for 0.3...19.2 kbps,
500 m for 38.4 kbps,
350 m for 76.8 kbps,
250 m for 115.2 kbps,
200 m for 250 kbps;
cable type LIYCY 3 x 2 x 0.14. T(A)/T(B) and R(A)/R(B) twisted in pairs
To ensure interference-free operation for cable lengths > 50 m, you must
install a terminating resistor of approx. 330 Ω at the receiver end.
DIN 66259 Parts 1 and 3, EIA-RS422/485, CCITT V.11
CM PtP communications module (6ES7137-6AA01-0BA0)
Equipment Manual, 03/2021, A5E03790792-01