Siemens SIMATIC ET 200SP HA Equipment Manual - Page 20

Browse online or download pdf Equipment Manual for Industrial Equipment Siemens SIMATIC ET 200SP HA. Siemens SIMATIC ET 200SP HA 44 pages. Distributed i/o devices busadapter for distributed i/o
Also for Siemens SIMATIC ET 200SP HA: Manual (32 pages), Manual (50 pages), Manual (34 pages), Manual (38 pages), Equipment Manual (50 pages), Equipment Manual (38 pages), Equipment Manual (46 pages), Equipment Manual (42 pages), Equipment Manual (44 pages), Equipment Manual (36 pages), Equipment Manual (38 pages)

Siemens SIMATIC ET 200SP HA Equipment Manual
Installation
4.4 BusAdapter BA 2xLC
Installing a BusAdapter to distributed I/O
To connect PROFINET IO to the device via the BusAdapter BA 2xLC, proceed as follows:
1. Plug in the BusAdapter and screw it tight.
2. Remove the protective caps of the LC plug connector, if present.
3. Grasp the assembled LC plug connector on the enclosure and insert it into the PROFINET
socket on the BusAdapter BA 2XLC until it clicks. The LC plug connectors are coded to
ensure correct connection.
4. Secure the PROFINET IO cable to protect the plug from pulling.
Installing BusAdapter BA 2xLC
Note
The figure below is a basic representation using the ET 200SP HA as an example; it is also valid
for other distributed I/O devices.
Figure 4-4
Additional information
You can find information about the installation guidelines and installation of fiber optic cables
in the documentation "SIMATIC NET; Industrial Ethernet / PROFINET; Passive Network
Components (https://support.industry.siemens.com/cs/ww/en/view/84922825)".
20
CAUTION
Risk of damage to eyes
Do not look directly into the opening of the optical transmitter diodes. The emitted light
beam could damage your eyes.
BusAdapter BA 2xLC
LC connector
PROFINET IO cable: Fiber-optic cable
Interface module
Connecting a PROFINET IO cable to the device via BusAdapter BA 2×LC
BusAdapter for Distributed I/O
Equipment Manual, 09/2019, A5E39261458-AB