Also for Siemens SIMATIC ET 200SP HA: Manual (32 pages), Manual (50 pages), Manual (34 pages), Manual (38 pages), Equipment Manual (44 pages), Equipment Manual (50 pages), Equipment Manual (38 pages), Equipment Manual (46 pages), Equipment Manual (42 pages), Equipment Manual (36 pages), Equipment Manual (38 pages)

Siemens SIMATIC ET 200SP HA Equipment Manual
Note
You can avoid the derating by deactivating channels 8 to 16.
Test current for signal state "0"
Note
If the "Check for wire break" parameter is activated, a test current flows, even if the signal state
for the output is "0" (singular mode: Approx. 700 μA, redundant operation: approx. 1.4 mA).
Cycle time
The cycle time describes the time slice in which signals from the inputs are acquired and
processed. The cycle time of the I/O module is 1 ms.
DQ 16x24VDC/0.5A
Equipment Manual, 10/2021, A5E39265993-AD
Technical specifications
35