3 Program configuration
6. (Optional) Also set "IdleTime" to 0 if your do not need it for your application.
(Optional) Delete the "Interlock", "Permit" and "Protect" blocks in the example if
you do not need them.
Incorrect configuration and operation can lead to accidents and damage to
CAUTION
the system!
To ensure proper and safe operation of your system, it is necessary to integrate
various protective mechanisms into the program, depending on the drive, system
structure, and application, and to parameterize the MotSpdCL block and the
drive appropriately.
The necessary program structure and the required parameterization of the
blocks of your project may, therefore, differ from the application example.
Failure to observe this warning may result in accidents and damage to the
system.
More information on the "MotSpdCL" block and its setting options and feature
bits can be found in the PCS 7 Advanced Process Library manual.
https://support.industry.siemens.com/cs/ww/en/view/109781589
3.2.2

FB Drive

Interconnect tags
1. In the CFC plan, select the input "PZDIn1" of the "FbDrive" block. Right-click to
open the context menu and select "Interconnection to Address..."
Choose the first input word of the process image of the G120X
(here: "IW512_G12x").
All other input and output words will be automatically connected by the driver
generator during compilation.
Figure 3-6
Integration of a SINAMICS G120X frequency converter in PCS 7
Entry ID: 109793986,
V1.0,
09/2021
20