3.1.1.1. Nodal block MAoSLi_MD_pDB (FB161)
The block has to be embedded between ‚SL_ORG_ASDU' of the target application (Slave) and
‚S7_IEC_Config' of the source application (Master).
The block transfers the information received by telecontrol messages from the Master connection to the
Slave connection. In the simplest case it is carried out "transparent" i.e. the information are transferred 1
to 1 without any pre-processing.
Illustration as CFC-block with default values
Important features are:
With minor effort of parameterization much information (‚max_No_of_Images') can be pro-
cessed:
- Single indication with TK 1,2,30
- double indication with TK 3,4,31
- transformer tap with TK5,6,32
- Bit pattern with TK7,8,33
Readings for the default adjustments can be taken from the corresponding variable comment.
On the other hand only a minimum of mandatory inputs are required.
The interconnection of ‚P_Application_Src', ‚ASDU_Adr_Src' and ‚P_SLi' is a minimum require-
ment.
automatic update of the image-DB with filter possibility for
defined address bands with ‚First_Info_Adr_Src', ‚Last_Info_Adr_Src'
-
certain information types with ‚Filt_15_13_11_9_7_5_3_1'
-
Adjustable processing per information type
- Priority
- time stamp
- GI (in parallel to the general interrogation (GI) a group interrogation is supported)
- Transfer also without changes
Automatic designation of all information with status not topical (NT) in case of disturbed connec-
tion to the subordinated station.
Optional assignable parameter block for
-
Individual quantity structure
-
Address conversion (of the information object address)
-
parameterizable threshold for measured values per information
-
possibility of image access (diagnosis / further processing)
SIPLUS RIC IEC on S7 V1.5
Functional description
CALL
Comp_ID
Para_Image_DB
max_No_of_Images
P_Application_Src
ASDU_Adr_Src
First_Info_Adr_Src
Last_Info_Adr_Src
Filt_15_13_11_9_7_5_3_1 :=
P_SLi
Tx_Prio_L
Tx_Prio_H
PrioH_15_13_11_9_7_5_3_1:=
wTime_15_13_11_9_7_5_3_1:=
Inro_QOI
IC_15_13_11_9_7_5_3_1
TwoC_15_13_11_9_7_5_3_1 :=
Threshold_Val_ME
FB_RetVal
IM_DB_No
No_used_IMs
New_Image
Illustration in AWL with fractional parameter supply
- measured value normalized value with TK9,10,34
- measured value with scaled value with TK11,12,35
- measured value with short floating point number
with TK13,14,36
- integrated totals with TK15,16,37
Page 11 of 28
"MAoSLi_MD_pDB" , DB261
:=
:=162
:=
:=#P_Appl_MA
:=L#111
:=L#1
:=L#20000
:=#P_Sli_Sl
:=
:=
:=
:=
:=1.000000e+001
:=MW200
:=MW202
:=MW204
:=M206.0
©SIEMENS AG 2013