Siemens SIPLUS RIC IEC on S7 Manual - Page 12
Browse online or download pdf Manual for Industrial Equipment Siemens SIPLUS RIC IEC on S7. Siemens SIPLUS RIC IEC on S7 28 pages. Addon nodal blocks version v1.5
3.1.1.2. Block parameter with its default assignment and short comment
FB161
Comp_ID
Para_Image_DB
max_No_of_Images
P_Application_Src
ASDU_Adr_Src
First_Info_Adr_Src
Last_Info_Adr_Src
Filt_15_13_11_9_7_5_3_
1
P_SLi
Tx_Prio_L
Tx_Prio_H
Pri-
oH_15_13_11_9_7_5_3_
1
wTime_15_13_11_9_7_5
_3_1
Inro_QOI
IC_15_13_11_9_7_5_3_
1
TwoC_15_13_11_9_7_5
_3_1
Threshold_Val_ME
FB_RetVal
IM_DB_No
No_used_IMs
New_Image
SIPLUS RIC IEC on S7 V1.5
Functional description
Type
Default
IN
BYTE
B#16#0
IN
INT
0
IN
INT
256
IN
DWORD
DW#16#0
IN
DINT
L#65535
IN
DINT
L#1
IN
DINT
L#16777215
IN
BYTE
B#16#FF
IN
DWORD
DW#16#0
IN
INT
1
IN
INT
0
IN
BYTE
B#16#8F
IN
BYTE
B#16#FF
IN
BYTE
B#16#14
IN
BYTE
B#16#7F
IN
BYTE
B#16#0
IN
Real
0.0
OUT
WORD
W#16#0
OUT
INT
0
OUT
INT
0
OUT
BOOL
FALSE
Page 12 of 28
Block-comment / short description
Identifier for Diagnostic-Functions
Number of a para-/image-DB; with 0 a DB will
be created at runtime
Default: 256; dimension of dynamic generated
data block for the images
Pointer
which
has
to
'S7_IEC_Config' - Module (Source of info)
Default: 65535=FFFFh -> All;
Default: 1
Default: max=16777215=FFFFFFh;
TI-Filter for IT/MEC/MEB/MEA/BO/ST/DP/SP:
Def: all TIs are forwarded (B#16#FF)
must
be
connected
SL_Org_ASDU - Module
Priority of transmission with Prio L: 0 (highest) -
15 (lowest) Default = 1
Priority of transmission with Prio H: 0 (highest) -
15 (lowest) Default = 0
Priority for transmission: 0: Low, 1: High / De-
fault = B#16#8F (MEs=Prio Low)
Transmission with(1) or without(0) Timestamp if
COT<20(requested);Def = B#16#FF
0: No Reaction; 20 (=14hex,default) General
interrogation; 21-36 -> Group 1-16
active. TIs will be transmitted within an interro-
gation; Default: B#16#7F
active. TIs will be forwarded without change of
val/state, if rcv. COT<20. Def:0;
0.0 without (def), >0: Threshold value (digits) for
forwarding of measured val.
positive
Values
->
ok;
(16#8xxx) -> Error
DB number for the internal process image, cre-
ated by this module
Number of information, actually placed in the
image data block
Signals that the number of Images has been
increased within this cycle
I IA CE
be
connected
to
with
P_to_SLi
from
negative
Values