Also for Siemens Sivacon S8: Operating Instructions Manual (7 pages), Operating Instructions Manual (24 pages), Manual (11 pages), Operating Instructions Manual (11 pages), Operating Instructions Manual (19 pages), Operating Instructions Manual (12 pages), Operating Instructions Manual (29 pages), Operating Instructions Manual (13 pages), Operating Instructions Manual (24 pages), Operating Instructions Manual (11 pages), Operating Instructions Manual (9 pages), Operating Instructions Manual (15 pages), Manual (11 pages), Operating Instructions Manual (9 pages), Repair Documentation (44 pages), Instructions Manual (12 pages), Operating Instructions Manual (11 pages), Operating Instructions Manual (18 pages)

Siemens Sivacon S8 Operating Instructions Manual
6 Adquisición de los instructivos de los aparatos
Los instructivos de la aparamenta de SIEMENS se pueden obtener en
la siguiente dirección de Internet:
http://www.siemens.com/lowvoltage/technical-support

7 Atornillado de las conexiones

PRECAUCIÓN
Apretar los tornillos de conexión con el par de apriete
indicado y, a continuación, identificarlos.
De esta manera se evitan conexiones sueltas y, por
tanto, la causa de incendios y daños en aparatos y
cables. Los pares de apriete excesivos pueden dañar el
aparato y la unión atornillada. Donde sea posible se
recomienda ejercer contrapresión con una herramienta
apropiada al apretar los tornillos.
Conexiones de barras o terminales sucias u oxidadas
deben ser limpiadas en las superficies de contacto antes
de realizar la conexión.
Tipo de conexión /
Connection type
6

6 Procurement of switchgear operating instructions

The operating instructions for SIEMENS devices are available under
the following internet address:
www.siemens.com/lowvoltage/technical-support

7 Bolting of connections

CAUTION
Apply the given torque to connection bolting and mark the
position.
Thus, loose connections and herewith the cause for fires
and damages to devices and cables can be avoided.
Excessive torque may damage the device and connection
bolting! Where possible, we recommend holding the
opposite nut with a suitable tool.
Soiled or oxidized connection bars or cable lugs must be
cleaned on contact surfaces before connecting.
Unión atornillada /
Arandela Belleville /
Conical spring washer
DIN 6796
Bolting
con arandela de seguridad /
with locking edge washer
8PQ9800-7AA72