Testing the system:
(Make sure that this test will not trigger an alarm to the rest of the system)
The system sends a SMS with the following text in these cases:
1.
Power up – "Smoke Vent Monitor powered up"
2.
Disconnect 230VAC – "MESSAGE FROM SMOKE VENT –
SYSTEM NEEDS ATTENTION!"
3.
Reconnect 230VAC – "MESSAGE FROM SMOKE VENT –
SYSTEM OK"
4.
Fire switch pressed – "MESSAGE FROM SMOKE VENT –
SYSTEM NEEDS ATTENTION"
5.
Fire alarm reset – "MESSAGE FROM SMOKE VENT – OK"
Be aware that the system will only send one SMS in the event of an alarm
or fail. If fail occurs before the alarm, then the user will only receive one
SMS and in this case it will be the "fail message" SMS.
Control of mobile network connection:
Since the modem uses external mobile network operators, we recommend
checking the mobile connection regularly, by forcing the system into failure
mode.
EN
Page 3/5
Guide for changing SIM card & phone number on
existing system:
1.
Disconnect power
2.
Change the SIM card. See Figure 1.
3.
Connect USB cable to the modem. See Figure 2
4.
Download software from www.Actulux.dk/Techn. Info/Software
5.
Power up system
6.
Wait for 10 seconds
7.
Run ConfigureModem.exe – Select COM port and enter phone
number - > Press then Phone Setup. See figure 6
8.
Disconnect USB cable
9.
Disconnect modem power
10.
Reconnect modem power
Remember to verify that the system is up and running after using the
Actulux GSM Modem PC software. To do this, follow the steps in the
"Testing the system" section of this document, page 3.