Ariston GENUS 41-116-01 Service Manual - Page 12

Browse online or download pdf Service Manual for Boiler Ariston GENUS 41-116-01. Ariston GENUS 41-116-01 44 pages. Type c
Also for Ariston GENUS 41-116-01: Installation Instructions Manual (32 pages)

Ariston GENUS 41-116-01 Service Manual
Soft-light
Max Heating
Anti-cycling
Device
Adjustment
Adjustment
R
12
Supplied By www.heating spares.co Tel. 0161 620 6677
10. Remove the pipe from the pressure gauge and connect screw "C" to the
pressure outlet in order to seal off the gas.
11. Carefully check the pressure outlets for gas leaks (valve inlet
and outlet).
IMPORTANT!
Whenever you disassemble and reassemble the gas connections, always
check for leaks using a soap and water solution.
Setting the anti-cycling device
This appliance is equipped with a potentiometer which delays the ignition of
the heating control and is situated on the P.C.B. (see the electrical diagrams).
By adjusting the potentiometer, it is possible to change the time interval
between the burner shutting down and its next ignition.
It is preset at 1 minute and can be adjusted from 0 to 2 minutes.
Use this control in particular situations where continuous shutting down and
ignition of the main burner occurs.
Q
Fig. 1.25
Fig. 1.26

Removing the spark generator (SIT Sigma gas valve)

1. Disconnect ignition leads "Q" by pulling upwards
(see fig. 1.25) ;
2. Remove the screws "R" (see fig. 1.26) with a Pozidrive
No. 2 star tip screwdriver;
3. Remove the spark generator.
Fig. 1.27
B005