CALEFFI 570951 Manual - Page 12
Browse online or download pdf Manual for Water Filtration Systems CALEFFI 570951. CALEFFI 570951 16 pages. Reusable cartridge for filling and demineralisation units 5741 series
Installation
2
B
3
4
5
6
7
8
To enable use of the cartridge, the 5741 series filling and
demineralisation unit must be correctly installed, as shown in the
specific instruction sheet.
Connection of the reusable cartridge also requires the use of the
hose kit code 570901.
Remove the yellow screw plug from the cartridge connections.
1
Caution: the yellow screw plugs must never be disposed of;
they are used for connection protection during storage and
transport.
2
Connect the hose to the untreated water connection on the unit
and the cartridge inlet connection (position
hose to the pure water connection on the unit and cartridge
outlet connection (position B).
Open both air vents on the cartridge cover (unscrew both white
3
screws through a few turns).
4 Only open the shut-off valve upstream and
Close both air vents on the cartridge cover.
5
Open the air vents on the filling unit and discharge all air until
6
water leaks from the valve, then close them.
Switch the conductivity measuring cell on to verify the
7
effectiveness of the treatment.
Open the shut-off valve downstream and start
8
the system filling with demineralised water.
4
start filling the cartridge. Leave the air vents
open until the cartridge is completely full
(water leaking from air vent).
). Connect the