Diversa WORXI32-P-N Installation Manual
Browse online or download pdf Installation Manual for Accessories Diversa WORXI32-P-N. Diversa WORXI32-P-N 2 pages. Occupancy & vacancy sensors - recessed ceiling, passive infrared (pir), 347vac
Installation Guide
PART NO.
FEATURES
• Commercial grade components for long term reliability
WORSI32-P-N
standard lens, PIR,
• Straightforward wiring for quick installation
347Vac, 2-pole,
photo sensor
• Factory configured for the most common applications
WORXI32-P-N
• DIP switches and dials for advanced functionality
extended range lens,
PIR, 347Vac, 2-pole,
• Photo Sensor for Natural Daylight control
photo sensor
Operation
Diversa 347Vac sensors draw control power directly from the lighting circuit they are intended to control. When in
operation the sensor will detect initial motion using Passive Infrared (PIR); once motion is detected, the internal
contact will close. Motion through PIR is used to maintain the occupied condition as long as occupants remain
within coverage range of Sensor.
DIP Switches
Manual Override Button
(Shown with cover
plate removed)
Time Delay Dial
Ranges from 30s to 30 min.
Full turn Clockwise for Auto Time
Full turn Counterclockwise for Test Mode
Photo Level Dial
Used to determine light
level for Photo Functions
SPECIFICATIONS
Power
• 347Vac
• 60Hz
Contact Ratings
• 347Vac - 800W
Power Consumption
• 5.7mA
Approvals
• Certified to UL 508, UL244A, CSA C22.2 #14
Environment
• Indoors, stationary, non-vibrating, non-corrosive atmosphere an
non-condensing humidity
• Ambient Operating Temperature: 32°F to 104°F (0°C to 40°C)
• Storage Temperature: -14°F to 140°F (-25°C to 60°C)
Diversa by Douglas Lighting Controls
Diversa Occupancy & Vacancy Sensors - Recessed Ceiling, Passive Infrared (PIR), 347Vac
Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor
Wiring
Instructions
Diversa 347Vac sensors include #14AWG wiring leads. Use appropriate sized wire nuts for connecting wires.
CAUTION: Turn power off at the circuit breaker before working on sensor. According to NEC 240-83(d), if the branch
circuit breaker is used as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked SWD.
All installations should be in compliance with National Electric Code (NEC) and all state, provincial, federal, and local
codes.
Line
Neutral
Load
Sensor Location Guidelines
To optimize the performance of Diversa Sensors, please review the coverage pattern, range, and model to
match with the application. Room dynamics will change when people and furniture are occupying the space.
Test Mode LED
In some rooms, after move in, some sensors may require adjustments.
• Ensure that the sensor is at least 30 inches away from air handlers/registers and not pointed directly at
windows
• Check that you are installing the right product (check the product model number) as per the drawings
Auto Time LED
Sensor Location Guidelines for "P" models
• Place outside the direct cone of light from fixtures
• Between 3 to 12 feet from windows
• As close as possible to the fixture being controlled
• Above the least illuminated space in the work area
• Away from lighting that is not being controlled by the sensor
DIMENSIONS/MOUNTING
inches (mm)
Unit attaches to mounting ring with
•
screws or it can be mounted into an
octogan box.
Ceiling tile
0.88"
Mounting
Wire
(2 2 )
ring
2.0"
(52)
4.17"
3 0 ° Tilt
(106)
DIPs and Dials
under cover
plate
•
The WOR sensor will fit an octagon
box. It is very important that conduits
be attached at opposite ends of the
box.
Conduit
Octagon Box
• Use a 2 1/8 " or more, deep box.
If the box is less, use the spacer ring.
2-pole
No Neutral
Black
Blue
Black/White
Blue/White
Load
Switch
Switch
White
www.douglaslightingcontrols.com
Installation
Installing in Smaller Room (Standard Lens)
• Locate the sensor near the entrance door wall to prevent it from viewing out into the hallway.
• Positioning the sensor in this manner ensures that an occupant moves across the longest detection beam
upon entrance, utilizing the sensor's maximum PIR range.
• Optimal usage is to detect small motions such as hand movements
• Designed for a mounting height of 7-15 ft
Line
Neutral
Side View
9 ft
0 ft
Typical Enclosed O ce
Extended Lens for Larger Rooms
• Place the sensor near the center of the room ceiling. Locate it so the approximate distance of 27ft in
or in dead center of room.
• Tilt the lens to aim the detection zone to the bottom of the door.
• Positioning the sensor in this manner ensures that the beam does not reach outside the room without
reducing sensitivity.
• Optimal usage is to detect large motions such as walking.
• Designed for a mounting height of 7-15ft.
27ft
C
27ft
Side View
9 ft
0 ft
Typical Classroom
14040700-C
Top View
14 ft
7 ft
0 ft
7 ft
14 ft
14 '
12 ' 10 '
6 '
3 '
0 '
3 '
6 '
10 '
12 '
14 '
Top View
27 ft
14 ft
0 ft
14 ft
27 ft
27 '
16 '
9 '
3 '
3 '
0 '
9 '
16 '
27 '