TB2 PROGRAM Connections
Refer to Fig. 11. The FT208 Monitor must have a program module installed in the PGM terminals ONLY
during programming of the monitor. This connection must be left open for normal operation. See the
Programming Section of this manual for detailed instructions about programming this unit.
Programming
Overview
Before the FloTech FT208 Monitor can be put into service, it must be programmed. This procedure informs the
monitor which inputs have sensors attached. These inputs are then labeled as ACTIVE sensors. The remaining
inputs that do NOT have sensors attached are labeled as INACTIVE inputs. This insures that a PERMIT signal
will be issued only if ALL of the following conditions are met:
All active overfill sensors are dry.
All inactive overfill sensors are not connected.
All active retain sensors are dry or the Retain Reset button has been pressed.
All inactive retain sensors are disconnected.
The AUX input is jumpered or made through an external contact.
If ANY of the above conditions are not met, the PERMIT signal will not be generated.
Programming is accomplished in the following manner:
Procedure
To program the FT208 monitor:
1. Turn the power to the unit off.
2. Remove the reset switch wires from TB2.
3. Connect the programming module (10459) into TB2 bottom four contacts marked "PROGRAM, GND,
RETAIN RESET, GND". Switches should be face up.
4. Move SW1 to "PRGM" position.
FloTech Programmable CheckMate Retain / Overfill Monitor
Retain Reset and AUX Connections
12
10466 REV N
Fig. 10
FT208 CheckMate