Arthur Grillo DPC200 Installation And Operation Manual - Page 8
Browse online or download pdf Installation And Operation Manual for Controller Arthur Grillo DPC200. Arthur Grillo DPC200 16 pages. Differential pressure controller, low pressure sensor with pi-control-mode
Also for Arthur Grillo DPC200: Manual (7 pages), Installation And Operation Manual (14 pages)
OPERATION
4.4 Electrical connection
DPC200
∆P
Alarm output: Open Collector
1.
Unscrew screws of the front cover.
2.
Open front cover.
DPC200
3.
Use M16 x 1,5 screws for connecting to terminals
4.5 Zero adjustment
∆P
Regardless of the menu the zero point can be readjusted with a small bar magnet without
opening the housing.
Alarm Ausgang: Open Collector
∆P
5.
Operation
5.1 Start menu
For operating the menu, unscrew the front cover to reach buttons T1 and T2.
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
N S
1
+ Versorgung: 10...30 Vdc;
2
- GND
3
+ Ausgang 0...10 V
Doc.-no.: DPC200_01_EN
+ 10...30 Vdc or 24 Vac (±15%) excitation
- GND (return)
+ 0...10 Vdc output
- GND (return)
dry contact
open: Setpoint 1
close: Setpoint 2
Alarm output
high ohm:
alarm off
low ohm:
alarm on
maximum customer circuit 30 Vdc / 30 mA
+ 10...30 Vdc oder 24 Vac (±15%) Versorgung
- GND
+ 0...10 Vdc Ausgang
- GND
Potentialfreier Kontakt
Adjustment:
offen:
Sollwert 1
The device is in measuring mode or con-
geschlossen: Sollwert 2
troll mode and not within the menu:
Alarm Ausgang
hochohmig: Alarm aus
niederohmig: Alarm an
•
Remove the hoses from the nozzles.
maximaler externer Stromkreis: 30 Vdc / 30 mA
•
Hold the bar magnet (N/S) to the zero
point adjustment for a short period of
time.
The new zero point will be stored.
24 Vac +/-15%
Issue: 11/2015