The following abbreviations apply in the manual:
AL ‐ alarm loop
FACP‐ fire alarm control panel
IR – infrared
1.1 The detector is designed to detect smoky fires inside large premises.
1.2 Detector consists of 2 units: transmitter (Tx) and receiver (Rx).
1.3 The detector transmits the Fire and the Fault messages. The detector transmits
the Fire message when infrared radiation flux between Tx and Rx is slackened by smoke in
specified number of times, and the Fault message when the infrared radiation flux is
completely obscured. These messages are indicated with red LED indicators on the
receiver.
1.4 The Fire outgoing signal retains after affecting with combustion aerosol
products has been ceased. You can reset the detector to standby mode switching off the
mains supply for at least 5 s.
1.5 The detector is designed for continuous‐running operation with 12/24V DC
FACP or intruder‐fire control panels.
2.1 Detection range
2.2 D.C. voltage range
2.3 Tx current consumption in standby mode ≤1 mA
2.4 Rx current consumption in standby mode ≤1 mA
2.5 Rx current consumption in fire mode
2.6 Rx current consumption in fault mode
2.7 Rx voltage drop in fire or fault mode
2.8 Tx voltage drop in standby mode
2.9 Start‐up time
2.10 Dimensions of the detector's units (w/o brackets)
2.11 Weight
2.12 Permissible angles of mechanical adjustment in horizontal plane ≥±90 °
Permissible angles of mechanical adjustment in vertical plane ≥±45°
2.13 Operating temperature range from – 30 to 55 °С
Relative humidity 93%
2.14 Average lifetime ≥10 years
ARTON‐DL smoke detector
Manual
1 dB attenuator
2 dB attenuator
2 TECHNICAL SPECIFICATIONS
3 ITEMS SUPPLIED WITH THE DETECTOR
Name
1 FUNCTION
10 ÷ 30 V
25+5 mA
≥8 V
≥8 V
≤10 s
1,5 kg
Quantity
1
Receiver – 1 pc.
Transmitter – 1 pc.
1
1
1
10 ÷ 100 m
8+1,6 mA
67х100 mm