The following abbreviations apply in the manual: 
AL ‐ alarm loop 
FACP‐ fire alarm control panel 
IR – infrared 
1.1 The detector is designed to detect smoky fires inside large premises. 
1.2 Detector consists of 2 units: transmitter (Tx) and receiver (Rx).  
1.3 The detector transmits the Fire and the Fault messages. The detector transmits 
the Fire message when infrared radiation flux between Tx and Rx is slackened by smoke in 
specified  number  of  times,  and  the  Fault  message  when  the  infrared  radiation  flux  is 
completely  obscured.  These  messages  are  indicated  with  red  LED  indicators  on  the 
receiver. 
1.4  The  Fire  outgoing  signal  retains  after  affecting  with  combustion  aerosol 
products has been ceased. You can reset the detector to standby mode switching off the 
mains supply for at least 5 s. 
1.5  The  detector  is  designed  for  continuous‐running  operation  with  12/24V  DC 
FACP or intruder‐fire control panels.  
2.1 Detection range                                                                   
2.2 D.C. voltage range 
2.3 Tx current consumption in standby mode                                          ≤1 mA 
2.4 Rx current consumption in standby mode                                            ≤1 mA 
2.5 Rx current consumption in fire mode 
2.6 Rx current consumption in fault mode 
2.7 Rx voltage drop  in fire or fault  mode 
2.8 Tx voltage drop in standby  mode 
2.9 Start‐up time                                                 
2.10 Dimensions of the detector's units (w/o brackets) 
2.11 Weight   
2.12 Permissible angles of mechanical adjustment in horizontal plane    ≥±90 ° 
         Permissible angles of mechanical adjustment in vertical plane       ≥±45°  
2.13 Operating temperature range                                                           from – 30 to 55 °С 
         Relative humidity                                                                              93%     
2.14 Average  lifetime                                                                               ≥10 years 
 
 
 
ARTON‐DL smoke detector 
 
Manual  
1 dB attenuator 
2 dB attenuator 
 
2 TECHNICAL SPECIFICATIONS 
 
 
 
 
 
3 ITEMS SUPPLIED WITH THE DETECTOR 
Name              
 
1 FUNCTION 
 
                                                    10 ÷ 30 V 
 
 
                                         25+5 mA   
                                         ≥8 V 
 
                                         ≥8 V 
 
                                 ≤10 s 
 
                                         1,5 kg 
 
Quantity
1
Receiver – 1 pc. 
Transmitter – 1 pc. 
1
1
1
 
                  10 ÷ 100 m 
                  8+1,6 mA   
                  67х100 mm 
Note