AKO 14801 Instructions - Page 2

Browse online or download pdf Instructions for Controller AKO 14801. AKO 14801 2 pages. Surface differential controller, 230 v, 2 relays

CURRENT
PASSWORD
TEMPERATURE
IF PROGRAMMED
SIMULTEANOUSLY
10 Sec.
IF L5=0
PASSWORD
ENTER
REQUEST
PASSWORD
PASSWORD
Level 2 Parameters
- In the desired menu of LEVEL 1 MENUS, press
accessed. The first parameter of the selected menu is displayed on the screen.
N
- Press
key to access the next parameter and key to return to the previous one.
P
- Pressing
, key, the controller returns to the LEVEL 1 MENUS.
Level 3 Values
- To DISPLAY the CURRENT VALUE of any parameter, select the required one and press
Once it is displayed, you can CHANGE VALUE, pressing
- Press SET key to ACCEPT THE NEW. The programming returns to LEVEL 2 PARAMETERS.
P
- Pressing
, key, the controller returns to the LEVEL 2 PARAMETERS.
REMARK: If no key is pressed for 25 seconds in either of the previous steps, the controller will
automatically return to the CURRENT TEMPERATURE display status without modifying any of
the parameters values.
6- Description of parameters and messages
Values in the Def. column are factory-set.
Level 1
Menus and Description
r1
Level 2
Pump Control (Relay R1)
Level 3
Description
SP1
Solar Set Point
Solar Differential (Hysteresis)
di1
CA1
Sensor 1 calibration (Offset)
Solar set point upper limit
HL1
(It cannot be set above this value)
Solar set point lower limit
LL1
(It cannot be set below this value)
Minimum time for pump (R1)
toF
Panels de-icing temperatura
AHF
(0=Disabled) (1=Enabled)
SP2
Panels De-Icing Temperature
di2
Panels De-Icing Differential (Hysteresis)
SP3
Maximum Temperature in Panels
di3
Panels De-Icing Differential (Hysteresis)
Relay polarity (Pump)
1
Pr1
(0=Normally open) (1=Normally closed)
r2
Level 2
Fan Control or Support Resistances (Relay R2)
Level 3
Description
Support resistance adjustment
SP4
temperature through probe 2
Support Resistance Differential (Hysteresis)
di4
CA2
Sensor 2 calibration (Offset)
Maximum temperature function in tank through probe 2
tAC
(0=Disabled) (1=Enabled)
Maximum Temperature in Tank
SP5
Tank maximum temperature
di5
diferencial (Hysteresis)
CnF
Level 2
GENERAL STATUS
Level 3
Description
Relay R2 function type
P0
(0=Fan) (1=Support resistances)
Test and SP1 keys disabled (0 = No)
P2
(1 = Test key disabled) (2=Test +SP1 keys disabled)
Initial parameters:
P3
(1=Yes, configure to "Def" and exit programming)
Address for units with communication
P5
Temperature display mode:
P7
(0=Integers in ºC) (1=One decimal in ºC)
(2=Integers in ºF) (3=One decimal in ºF)
Sensor to be displayed (1=Sensor 1) (2=Sensor 2)
P8
Sensor 1 type selection (0 = NTC) (1 = PTC)
P9
Av. Roquetes, 30-38 | 08812 Sant Pere de Ribes | Barcelona | España
Tel. (34) 938 142 700 | Fax (34) 938 934 054 | e-mail: [email protected] |
Apartado (P.O. Box), 5 | 08800 Vilanova i la Geltrú | Barcelona | España
LEVEL 1
LEVEL 2
LEVEL 3
MENUS
PARAMETERS
VALUES
CURRENT
VALUE
EXIT TO
LEVEL 2
DISPLAY
EXIT
EXIT TO
LEVEL 1
PROGRAMMING
O
. key. LEVEL 2 PARAMETERS programming is
N
Q
or
key.
Values
Mín.
Def.
(ºC/ºF)
LL1
7.0
(ºC/ºF)
1.0
3.0
(ºC/ºF)
-20.0
0.0
(ºC/ºF)
LL1
15.0
(ºC/ºF)
0.0
3.0
(Sec.)
0
10
0
(ºC/ºF)
-9.0
5.0
(ºC/ºF)
1.0
2.0
(ºC/ºF)
0.0
95.0
(ºC/ºF)
1.0
2.0
0
Values
Mín.
Def.
(ºC/ºF)
0.0
40.0
(ºC/ºF)
1.0
2.0
(ºC/ºF)
-20.0
0.0
(ºC/ºF)
0
(ºC/ºF)
0.0
70.0
(ºC/ºF)
1.0
2.0
Values
Mín.
Def.
0
0
0
0
0
1
0
tid
Level 2
Level 3
Access password to parameters and information
L5
Parameters transfer:
L6
(0=Disabled) (1=Send) (2=Receive)
PU
Program version (Information)
MESSAGES
Password request to enter programming parameters
PA
NEW
or SOLAR SET POINT (SP1)
VALUE
Flashing with temperature - Over Temperature in Probe 1 ³
Ht1
(Maximum Temperature in Panels)
Flashing with temperature - Over Temperature in Probe 2 ³
Ht2
(Maximum Temperature in tank)
Flashing with temperature - Low Temperature in Probe 1 £
Lt1
(Maximum Temperature in Panels)
tSt
Test mode. R1, R2 manually enabled.
CPY
Parameters received from the parameters server.
Sensor 1 failure (Open circuit, crossed, NTC temp.> 110ºC or temp.<-55ºC
E1
PTC temp.> 150ºC or temp.<-58ºC)
E2
Sensor 2 failure (Open circuit, crossed, NTC temp.> 110ºC or temp.<-55ºC)
EE
Memory failure
7- Parameters transfer
Portable server
AKO-14918 portable server, with no
power supply, in which parameters
programmed in a powered controller can
be copied by transfer. Parameters can be
O
transferred again from the server to other
.key.
identical powered controllers.
Storage dump or fast copy of the parameters entered in the portable server to
the controller: Press the key
supply until the display shows CPY, indicating that the transfer was made correctly.
Disconnect the controller and reconnect it to the power supply.
Storage dump can also be done from parameter L6=2.
8- Maintenance
Clean the controller surface with a soft cloth, soap and water. Do not use abrasive
detergents, petrol, alcohol or solvents.
9- Warnings
The use of the unit without observing the manufacturer's instructions may alter its safety
Máx.
qualification.
HL1
To ensure correct operation of the apparatus, only NTC type probes supplied by AKO should
5.0
20.0
be used.
Between -40 ºC and +20 ºC, when the NTC probe is extended up to 1.000 m with minimum
30.0
0,5 mm2 cable, deviation will be less than 0.25 ºC (Probe extension cable ref.
HL1
AKO-15586)
255
10- Operation and control of relays R1 and R2
0
1
50.0
Facility 1:
5.0
R1 = Pump
302
R2 = Support
5.0
resistances
0
1
R1
Máx.
Solar
R1
212
Differential
Pump
ΔT
5.0
(S1-S2)
SP1-di1
SP1
20.0
S1
R1
0
1
De-icing
Pump
temperature
in panels
212
SP2-di2
SP2
5.0
Maximum
Temperature
R1
In Panels
Pump
Máx.
S1
SP3
SP3+di3
0
1
S2
R2
Support
0
2
External
resistance
Support
Resistance SP4-di4
SP4
0
1
S2
0
255
R1
Maximum
Pump
Temperature
In Tank
1
3
SP5-di5
SP5
If E1 (Sensor 1 Failure) R1 = ON, R2 = OFF
1
2
If E2 (Sensor 2 Failure) R1 = XXX, R2 = OFF
0
1
AKO ELECTROMECÀNICA, S.A.L.
www.ako.com
We reserve the right to supply materials that might vary slightly to those described in our
Technical Sheets. Updated information is available on our website: www.ako.com
ACCES AND INFORMATION control
Description
Values
Transfer
AKO-14918
O
while the controller is being connected to the power
S1
Facility 2:
R1 = Pump
R2 = Fan
S2
R1
R2
ΔT > SP1
R1=ON
ΔT < SP1-di1
R1=OFF
Differential
R1
Solar
Pump
ΔT
(S1-S2)
S1 > SP2
SP1-di1
R1=XXX
S2 < SP2-di2
R1=ON
S1
R1
De-icing
R2
temperature
in panels
S1 > SP3+di3
R1=ON
SP2-di2
S1 < SP3
R1=XXX
Maximum
R1
Temperature
If R1=OFF or
R2
In Panels
(AHF=1 and S1<SP2-di2)
S1
S2 > SP4
SP3
SP3+di3
R2=OFF
S2 < SP4-di4
R2=ON
S2
R1
Maximum
Pump
Temperature
S2 > SP5
R1=OFF
In Tank
S2 < SP5-di5
R1=XXX
SP5-di5
If E1 (Sensor 1 Failure) R1 = ON, R2 = ON
If E2 (Sensor 2 Failure) R1 = XXX, R2 = ON
Mín. Def. Máx.
0
0
255
0
0
2
SP3
SP5
SP2
Power supply
Programming
R2
S1
S2
ΔT > SP1
R1=ON
ΔT < SP1-di1
R1=OFF
SP1
R1=XXX
S1 > SP2
R2=XXX
R1=ON
S2 < SP2-di2
R2=OFF
SP2
R1=ON
S1 > SP3+di3
R2=ON
R1=XXX
S1 < SP3
R2=OFF
or
R1=XXX
ΔT < SP1-di1
R2=OFF
S1 > SP5
R1=OFF
S1 < SP5-di5
R1=XXX
SP5