ASHAPOWER ROVER-5000LV-48V User Manual - Page 9
Browse online or download pdf User Manual for Inverter ASHAPOWER ROVER-5000LV-48V. ASHAPOWER ROVER-5000LV-48V 14 pages. Solar mppt pcu
ASHAPOWER SOLAR-PCU INSTALLATION & OPERATION GUIDE LINES
1) Battery bank setup :
Check each battery separately for specific gravity, same terminal volt
Do
not use old and new batteries together, either in parallel or in series.
join the batteries
cables to
2)
PV panel grouping:
Group the PV panel array using standard solar MC4 connectors and parallel
connectors as to the recommended grouping example chart provided. Good quality weather proof solar
DC cables
must be used
Place of Installation
:
3)
distance from the wa l
l.
4) DCDB / ACDB
& Surge protectos
in the circuit of o grid power plant, under the guidance of a qualified electrical engineer/electrician for safety
and long life of the power plant. Never use substandard electrical materials for wiring.
Now
Connect the battery
(Reverse polarity will spoil the
Connect the cables from PV panels to the solar positive and negative terminals of
PV panel voltage and polarity is
When the connected battery vo l tage reaches GRID to SOLAR preset vo l tage (default 14.2V)
glows ON indicating the battery is nearly full charge and ready to use the connected
indicator LED
inverter load.
When phase and neutral of grid power is connected to the concerned grid terminals ,
glows ON.
GUIDE LINES FOR QUICK CUSTOMER SETTINGS AND MAIN TECHNICAL SETTINGS
Quick customer settings menu is provided with 6 options
1) UPS / INVERTER mode ON/OFF selection
2) Grid Charging ON/OFF selection and Grid and solar charging priority selection.
Customer can select grid charging OFF option to avoid all kinds of grid power charging.
Two priority charging options are given.
Solar charging priority and grid charging priority
If Solar priority is selected, battery charging will be from solar power.If the battery terminal volt is below
the inverter low warning level (10.7default for 1 battery) grid power is also used for boosting the batteries.
When solar power is not available battery charging will be fully from grid power in 8 amps (default)
If Grid priority is selected device charges the battery both from grid and solar power simultaneously
giving priority to grid.eg.If the grid charger is preset to10 amps and solar charging current is available
above this value system charges battery drawing10 amps fully from grid power and available current
from solar.
3) Grid bypass ON/OFF Selection and Automatic grid to solar shifting selection
Three options are givn. If BV+PV+GRID option is selected system shifts to solar mode only if there is the
presence of grid supply,high battery terminal volt and solar PV presence.
If BV+PV option is selected system shifts to solar mode only if there is the presence of solar PV and
high battery terminal volt. If BV option is selected system shifts to solar mode whenever the battery
terminal volt becomes high from any charging source.
4) Gri - solar-V (grid to solar shifting volt selection)
5) Sol - grid-V (solar to grid shifting volt selection)
6) Sol - grid-Kwh (solar to grid shifting based on Kwh) (for Lithium batteries)
MODEL : ROVER-5000 LV-48V
and t i g ht them wel l .
(6sqmm,10sqmm)
Place the solar PCU on a fixed stand in a well ventilated area keeping a 6 inch
Avo i d exposure to ra i n, dusty area, direct sun l i ght or in area having high temperature.
It is recommended to connect DCDB / ACDB & lightning surge protectors
:
wires with correct polarity to the connection
device)
LCD display shows battery voltage and default function parameters.
correct solar charging starts indicating
Use
terminal block of the device
SOLAR CHARGING LED
9
and good backup
25 sqmm/16sq i nter l
i nkin g
the solar PCU.
If the
glowing
ON.
LOAD ON SOLAR
indicator
GRID POWER ON