7.3 Commissioning (See Also Section 6.0)
Use the "+" or "-" button to set speed function to 'Boost'.
From the home screen, press and hold "SET" and "COPY"
simultaneously for 3 seconds to open the installer level.
Press "COPY" once to move to 'Menu 2' 'Fan 1 Low'.
Press "PROG" once to 'Fan 1 Boost' (Extract/Exhaust fan).
Use the "+" or "-" button to set the desired speed (Factory default
speed is 50%).
Note: The installer level access will time out after 1 minute of inactivity
but will record any changes made to the settings.
Press "SET" to record the settings and return to the home screen.
Press "ESC" to discard the settings and return to the home screen.
10.
Fan 1 Commissioning Screen
Repeat the above steps for:
Fan 2 Boost (Supply/Intake fan) (Factory default speed is 50%).
Fan 1 Low (Extract/Exhaust fan) (Factory default speed is 20%).
Fan 2 Low (Supply/Intake fan) (Factory default speed is 20%).
'Max' speed can be set to a maximum of 99% (Factory default 80%).
Note: Low speed cannot be set higher than Boost speed and Boost
speed cannot be set higher than Max speed.
Press "SET" to record or "ESC" to discard the settings and return to
the home screen.
7.4 Automatic Heat Exchanger Bypass
7.4.1 Activation / Inactivation
From the home screen, press and hold "SET" and "COPY"
simultaneously for 3 seconds.
Press "COPY" as required to move to 'Menu 3', 'Bypass tEnp'.
Use the "+" or "-" button to set to 'on' or 'off' (OF) as required.
Press "SET" to record or "ESC" to discard the settings and return to
the home screen.
11.
HX Bypass Activation Screen
7.4.2 Setting Bypass Operating Temperature
From the home screen, press "TEMP" as required to move to menu
'T3'.
T3 is the target indoor temperature setting at which the heat
exchanger bypass mechanism operates to allow the extract air to bypass
the heat exchanger and is adjustable between +15°C and +25°C
(Factory default 20°C).
LAB1199R | OCTOBER 2023
Use the "+" or "-" buttons to set the operating temperature in steps
of 1°C.
Press "SET" to record or "ESC" to discard the settings and return to
the home screen.
12.
HX Bypass Temperature Screen
7.5 Automatic Humidity Controlled Boost
7.5.1 Activation / Inactivation
From the home screen, press and hold "SET" and "COPY"
simultaneously for 3 seconds.
Press "COPY" as required to move to 'Menu 7', 'IhuN'.
Use the "+" or "-" button to set to 'on' or 'off' (OF) as required.
Press "SET" to record or "ESC" to discard the settings and return to
the home screen.
13.
Humidity Boost Activation Screen
7.5.2 Setting Humidity Activated Boost Switching Level (%RH)
From the home screen, press "HUM" to move to the humidity (%
RH) activated boost setting (Factory default 60% RH – recommended).
Use the "+" or "-" buttons to set the humidity switching level in
steps of 1% RH (range 30- 85%RH).
Press "SET" to record or "ESC" to discard the settings and return to
the home screen.
14.
Humidity Boost Switching Level Screen