Domus HRX-aQ AQH200-B Handleiding voor installatie-instructies - Pagina 9
Blader online of download pdf Handleiding voor installatie-instructies voor {categorie_naam} Domus HRX-aQ AQH200-B. Domus HRX-aQ AQH200-B 12 pagina's. Range mechanical ventilation with heat recovery
7.6 Filter Reminder
The word 'Filter' will appear on the home screen after the set time has
elapsed. When this occurs, clean the filters (Section 8.0)
Note: The figure at the bottom of the screen indicates elapsed
operating time in hours. When the numbers are not flashing, they
indicate the elapsed time since the last filter reset. If "DAY" is pressed,
the numbers will flash and indicate the total elapsed operating time in
hours.
•
To reset the filter elapsed time reminder following cleaning, press
and hold "SET" for 5 seconds.
7.6.1 Adjustment and Inactivation
•
From the home screen, press and hold "SET" and "COPY"
simultaneously for 3 seconds
•
Press "COPY" as required to move to 'Menu 1' 'Filter'
•
Use the "+" or "-" buttons to change the time delay in steps of 50
hours as required or 'off'.
Note: The filter check reminder is factory set at the maximum of 3000
hours (approx. 4months - recommended). During adjustment, when this
maximum has been reached, the 'off' option can be accessed.
•
Press "SET" to record or "ESC" to discard the settings and return to
the home screen.
15.
Filter Reminder Adjustment Screen
7.7 Frost Protection Trigger Temperature Adjustment
•
From the home screen, press and hold "SET" and "COPY"
simultaneously for 3 seconds.
•
Press "COPY" as required to move to 'Menu 4', 'T5'.
Menu T5 sets the frost protection trigger temperature between -15°C
and +5°C (Factory default +1°C).
•
Use the "+" or "-" buttons to set the trigger temperature in steps of
1°C.
•
Press "SET" to record or "ESC" to discard the settings and return to
the home screen.
16.
Frost Protection Trigger Temperature Adjustment Screen
LAB1199R | OCTOBER 2023
7.8 Delay-On Timer Activation / Deactivation
•
From the home screen, press and hold "SET" and "COPY"
simultaneously for 3 seconds.
•
Press "COPY" once to move to 'Menu 5' 'Delay-on setting'.
The Delay-on setting provides a 3 minute delay before Boost speed is
engaged.
•
Use the "+" or "-" button to set to 'on' or 'off'.
Note: The Delay-on function will always be overridden by automatic
humidity sensing.
•
Press "SET" to record or "ESC" to discard the settings and return to
the home screen.
17.
Delay-On Activation Screen
7.9 Delay-Off Timer Activation / Deactivation
•
From the home screen, press and hold "SET" and "COPY"
simultaneously for 3 seconds.
•
Press "COPY" once to move to 'Menu 6' 'Delay-off setting'.
The Delay-off setting provides an adjustable run-on timer when Boost
speed is engaged – adjustable between 5 and 30 minutes or 'off'.
•
Use the "+" or "-" button to set the desired run-on time in 1 minute
steps (Factory default is off).
•
Press "SET" to record or "ESC" to discard the settings and return to
the home screen.
18.
Delay-Off Activation Screen
7.10 Optional Duct-Heater Operating Temperature (°C)
•
From the home screen, press "TEMP" as required to move to menu
'T4'.
T4 is the outdoor temperature setting at which an optional intake air
duct-heater switch can be activated and is adjustable between +5°C
and +12°C (Factory default 10°C).
•
Use the "+" or "-" buttons to set the activation temperature in steps
of 1°C.
•
Press "SET" to record or "ESC" to discard the settings and return to
the home screen.
PAGE 9