Ekinex EK-BW1-TP Snelstarthandleiding - Pagina 2
Blader online of download pdf Snelstarthandleiding voor {categorie_naam} Ekinex EK-BW1-TP. Ekinex EK-BW1-TP 4 pagina's. Knx voice control interface
i
Note. The RESET button is not directly accessible on the front
panel of the product. To access the button, open the front panel
of the delégo server using a small slotted screwdriver and exer-
ting a slight leverage effect in one of the side slots. Locate the
RESET button on the back of the vertical board at the bottom of
the device towards the KNX terminals.
Mounting
The device has degree of protection IP20, and is there-
fore suitable for use in dry interior rooms. The housing is
made for rail mounting according to EN 60715 in boards
or cabinets for electrical distribution. The installation is in
horizontal position, the correct position is when the KNX
bus terminal is located at the bottom and the terminals for
the outputs are located at the top.
For the installation of the device on the rail proceed as
follows:
• with the aid of a tool bring the locking device in the fully
lowered position (1);
• place the upper edge of the rear inner profile on the
upper edge of the rail (2);
• rotate the device towards the rail (3);
• push the locking device upward until it stops (4).
Before removing the device, be sure the inputs have been
disconnected and the bus terminal has been extracted
from its slot. Use a screwdriver to slide down the locking
device and remove the device from the rail.
i
Note. It is recommended that the installation of the device
always ensure the full accessibility of the front side to allow the
led visualization.
Power 12-24 Vdc
The connection to the power supply is made via the
screw terminals (1)+ and (2)- located on the removable
2-pin connector.
Clamp characteristics
• Screw tightening of conductors
• Max. conductor cross-section 2.5 mm2
• Recommended conductor stripping approx. 6 mm
• Max. torque 0.5 Nm
!
Warning! The electrical connection of the device may only be
carried out by qualified personnel.
Connection to the KNX bus network
The connection to the bus network is made via the KNX
terminal included in the scope of delivery and inserted
into the housing on the front of the device at the bottom.
KNX clamp characteristics
• Spring clamping of the conductors
• 4 conductor seats for each polarity
• Suitable for KNX bus cable with single conductors
between 0.6 and 0.8 mm diameter
• Recommended conductor stripping approx. 5 mm
• Colour coding: red = bus conductor + (positive), black =
bus conductor - (negative)
!
Warning! Only use KNX bus power supplies (e.g. ekinex EK-
AB1-TP or EK-AG1-TP) to supply the KNX bus lines. The use
of other power supply devices can impair communication and
damage the devices connected to the bus.
Configuration and commissioning
The configuration and commissioning of the voice con-
trol interface must be carried out by accessing the web
server integrated in the product. These activities must be
carried out in accordance with the design of the building
automation system carried out by a qualified professio-
nal.
2
EK-BW1-TP
Voice control
EK-BW1-TP
Voice control
bus KNX