Installation
Weld-in sleeve with draining feature
Install some weld-in sleeves at the proper angle to ensure automatic draining.
6.4

Installation factor

Where installation space is tight, walls have an impact on the ion flow in the liquid. This effect
can be compensated by the installation factor.
Installation factor in the transmitter is set via display, IO-Link or FlexProgram.
The installation factor depends on diameter and conductivity of the pipe socket as well as the
distance from wall to sensor.
In case of sufficient distance to wall (a > 20 mm), the installation factor f can be ignored (f =
1.00).
In case of inferior wall distance, the installation factor for electrically insulated pipes is larger (f >
1) respectively smaller (f < 1) for case electrically conductive pipes.
The installation factor can be identified by calibration solutions or approximately derived from
the diagram below.
0
1
Pipe wall electrically conductive
12
a
1.06
2
1.04
1.02
1
1
0.98
0.96
5
10
Operating Manual
15
20
25
2
Pipe wall electrically insulated
Baumer
30
35
40
mm
PAC50H/S | V1