1. When the burner is stopped, only the gas supply shall be
cut off, and the combustion auxiliary air should not be cut off
immediately. If the combustion auxiliary air is interrupted for
more than 5 minutes, the burner should be removed to
prevent damage to the burner and the flame detector.
2. When the gas is not completely closed, do not remove the
gas metal hose or the locking device
5.1 Burner Data
Burner
Input
Type
kW
92G50
10-30
5.2 Burner Adjust
Fix the burner on position, ensure that the burner does not slide by external forces. Connect the
burner oxygen hose to the combustion oxygen inlet. Connect the burner gas hose to the gas inlet.
Open the combustion oxygen valve and test the pressure at 1-15 mbar, which should be properly
adjusted according to the kiln pressure. Check and confirm that both the oxygen hose and the
gas hose are correctly and firmly connected. Open the gas valve and adjust the gas flow regulating
valve to ensure flame stability.
6.
Burner maintenance
Burners require routine inspection. Examination after first or long absence are particularly important.
For the first use, check that the seal of each interface is intact and not loose. After the burner is first
used normally, the burner needs to be checked. The pilot burner is checked weekly in the first month,
and at the second month, the inspection frequency can be extended to once in two weeks. Anderson
Anderson Thermal Soluions(Suzhou)Co., Ltd
F
igure 1: PBO92 Series air burner
Burner
Burner
OD
Length
(mm)
(mm)
27
300-950
Anderson Thermal Solutions – PBO92 Operation Manual
Attention!
Gas Flow
Gas Pressure
(Nm
/h)
3
Min
Max
Min
2
3
10
3
Oxygen
Pressure
(mbar)
(mbar)
Max
Min
15
10
Max
15