Auber Instruments WS Series Bedienings- en instructiehandleiding - Pagina 8
Blader online of download pdf Bedienings- en instructiehandleiding voor {categorie_naam} Auber Instruments WS Series. Auber Instruments WS Series 18 pagina's. Programmable pid temperature controller with dual probe
Ook voor Auber Instruments WS Series: Beknopte handleiding (15 pagina's), Beknopte handleiding (14 pagina's), Bedienings- en instructiehandleiding (18 pagina's), Beknopte handleiding (14 pagina's)
This section discusses how to configure the controller for a specific application. For most
sous vide cooking users, there is no need to read this section. The controller's default
setting is for most common configurations of sous vide cooking.
The controller parameters are divided into two groups.
A) The first group of parameters is related to the control performance. They need to be
adjusted based on the system to be controlled. Table 2 shows the list of these
parameters, their range and initial set value.
Table 2. List of control parameters and its initial settings under code 166.
Details about each parameter
P. Proportional band. It is in 0.1 degree units. This parameter controls the output
of the controller based on the difference between the measured and set
temperature. Larger the P number means the weaker the action (lower gain). e.g.
If P=100, the proportional band is 10 degree (100 x 0.1=10). When the sensor
temperature is 10 degrees below the proportional band (10 degrees below the
setting), the controller will have 100% output. When the temperature is 5 degrees
below the set point, the output is 50%. When the temperature is equal to the
setting, the controller will have 0% output (assuming integral and derivative
functions are turned off). This constant also affects both integral and derivative
action. Smaller P values will make the both integral and derivative action stronger.
Please note the value of the P is temperature unit sensitive. If an optimized P
value was found when operating the controller in Celsius, it needs to be multiplied
by 1.8 when changed to Fahrenheit.
On/off mode. If P is set to 0, the control mode will be changed from PID mode to
On/off mode. On/off mode should be used for controlling an external relay, a
solenoid valve, or a compressor of freezer. You also need to set the hysteresis
band (dead band) for the on/off mode. In the on/off mode, Integral and Derivative
parameters are not valid.
I. Integral time. The unit is in seconds. This parameter controls the output of the
controller based on the difference between the measured and set temperature
integrated with time. Integral action is used to eliminate temperature offset. Larger
numbers mean slower action. e.g. assuming the difference between the
8