Auber Instruments SYL-1813-MR Gebruiksaanwijzing - Pagina 2

Blader online of download pdf Gebruiksaanwijzing voor {categorie_naam} Auber Instruments SYL-1813-MR. Auber Instruments SYL-1813-MR 3 pagina's. Multifunction automotive gauge

AUBER INSTRUMENTS
Note 3. For adjusting the display value; applies only to the temperature
readings. Display = measurement * PSbF.
Note 4. Digital filter. Filt = 0, no filter; 1, weak; 2, medium; 3, strong.
Table 1. Sensor Input Type Options
Symbol
Input Type
TC, Type T
-200 ~ 400° C
T
TC, Type R
-50 ~ 1600° C
R
J
TC, Type J
-200 ~ 1200° C
TC, WRe3
WRE
0 ~ 2300° C
–WRe25
VDO
Vdo
water/oil
50 ~ 150° C
Temp
TC, Type S
-50 ~ 1600° C
S
K
TC, Type K
-200 ~ 1300° C
E
TC, Type E
-200 ~ 900° C
RTD,
P100
-200 ~ 600° C
PT100
RTD, Cu50
-50.0~ 150.0° C
Cu50
0~375Ω
375r
Pressure
0~75mV
75mV
Current
0~30mV
30mV
Display range
0~5V
5V
1-5V
1~5V
to -1999 ~ 9999
10V
10V
0~10mA
10mA
20mA
0~20mA
4 -–
4~20mA
20mA
(Note: TC, thermocouples.)
D.1.B) How to change basic parameters (see Figure 4)
Operation Mode
Enter Code
SET
0089
XXXX
SET
Figure 4. Basic Parameter Setting Flow Chart.
D.2 Alarm parameter (press SET then input code 0001 to enter)
D.2.A) Alarm parameters description
Symbol
Name
Description
AH1
J1 pull in value
AH1
AL1
J1 drop out value
AL1
2021.05
Range
Res.
Accy.
1° C (° F)
0.3%
1° C (° F)
0.3%
1° C (° F)
0.2%
1° C (° F)
0.2%
1° C (° F)
0.3%
1° C (° F)
0.3%
1° C (° F)
0.2%
1° C (° F)
0.2%
1° C (° F)
0.2%
0.1° C
0.5%
(° F)
0.2%
0.1%
0.1%
0.1%
can be set
16 bit A/D
0.1%
0.1%
0.3%
0.2%
0.2%
Symbol
Input Type
SET
SET
XXXX
inty
Input Low Limit
SET
XXXX
PuL
Input High Limit
SET
XXXX
PuH
Deci m al Point
SET
XXXX
DOT
Input Offset
SET
XXXX
psb
Range Coefficient
SET
XXXX
Psbf
Temperature Unit (C/F)
SET
X
corf
Digital Filter
X
FILT
end
Setting Range
-1999 ~ 9999
-1999 ~ 9999
AH2
AH2
AL2
AL2
End
End
Note 5a. Relay action setting.
1) Set AH1 = AL1, relay is disabled.
Impedance
2) Set AH1 > AL1, relay is for high limit alarm. See Figure 5 (left).
100K
3) Set AH1 < AL1, relay is for low limit alarm. See Figure 5 (right).
100K
100K
100K
(0.2mA)
100K
100K
100K
Figure 5. Reply (J1) action when the alarm is set as high alarm (left) and low
(0.2mA)
alarm (right).
(0.2mA)
Note 5b. AH2 and AL2 parameters should be ignored. They are associated with
J2 relay, which are not available in this gauge.
(0.2mA)
100K
D.2.B) How to change alarm parameters
The procedure to change alarm parameters is similar to the procedure for basic
100K
parameter setting shown in Figure 4 except the access code is 0001 instead of
100K
0089.
100K
100K
D.3. Peak value (press SET then input code 0037 to enter)
150Ω
D.3.A) Peak value description
150Ω
150Ω
Symbol
Name
MA
MA
MA-t
MA-t
MI
MI
MI-t
MI-t
End
End
SET
Note 6. Peak function is inter-locked.
1) When MA is turned off, MA-t cannot be set to "on".
SET
2) When MI is turned off, MI-t cannot be set to "on".
D.3.B) How to change peak value parameters
SET
The procedure to change the peak value settings is similar to the procedure for
changing basic parameters in Figure 4 except access code is 0037 instead of
SET
0089.
SET
D.3.C) Reset the peak value
The peak values is stored in the memory even the meter is powered off. To reset
SET
them, change display to show MA, MA-t, MI or MI-t. Then, press and hold "Λ"
key for 3 seconds. The display will show "- - - - ", indicating the memory (for all
SET
four parameters) is reset. The meter will start to catch the new peak after 2
seconds.
E. Application Examples
E.1 Exhaust gas temperature (EGT)
Auber's EGT probes are type K thermocouples. To read an Auber's EGT probe,
set the sensor type inty to "k" (k). The gauge is preset for the EGT application.
Wire the meter as the diagram below (Figure 6) and it is ready to go.
(Continue on next page)
Initial
Note
Setting
900
5a
800
WWW.AUBERINS.COM
N.A.
-
N.A.
-
Exit
Description
Setting Range
Maximum value
On/off
Time of maximum
On/off
Minimum value
On/off
Time of minimum
On/off
Exit
900
5b
800
Initial
Note
Setting
On
Off
6
Off
Off
P2/3