Danfoss REPI Series Handmatig - Pagina 3
Blader online of download pdf Handmatig voor {categorie_naam} Danfoss REPI Series. Danfoss REPI Series 3 pagina's.
Ook voor Danfoss REPI Series: Gegevensblad (4 pagina's)
Input signal management:
31
0: Input valid
1: Override Input: open
2: Override Input: close
Display room temperature or set-point
32
0: Room temperature 1: Set-Point
Configuration external sensor
33
0: B = 3950; 1: B = 3450; 2: B = 3900
3: User define (via network. default B = 3950)
34-38
N/A
39
Start temperature of Low temperature protection
40
Stop temperature of Low temperature protection
It will confirm itself 20 seconds later after setting and return to Off state.
Switch:
There is a 5 poles switch on PCB. The meaning is below:
Location
1
2
3
4
5
Mounting:
1. Open the back panel with
screwdriver.
Wiring diagram:
Note: Be sure to connect all the wires as per the wiring diagrams and keep it away from water, mud
and other material so as to prevent the unit being spoiled!
ON
120 ohm Resistance between AB wires
Port 1 Modulation 0 - 20mA
Port 1 Modulation 0 - 10VDC
Port 2 Modulation 0 - 20mA
Port 3 Modulation 0 - 10VDC
2. Connect the wires follow the
diagram.
REPI-2/2N
0
0
0
5℃/42℉
0-15℃/42-62℉
7℃/46℉
2-17℃/46-66℉
No Resistance between AB wires
3. Fix the base with screw.
Page 3 of 3
0 - 2
0 - 1
0 - 3
1℃/2℉
1℃/2℉
OFF
Off
Off
Off
Off
4. Fix the front panel and finish
the installation.
REPI-4/4N