DANLERS CZ HB ND Installatie-opmerkingen

Blader online of download pdf Installatie-opmerkingen voor {categorie_naam} DANLERS CZ HB ND. DANLERS CZ HB ND 2 pagina's. Controlzapp high bay controls

DANLERS CZ HB ND Installatie-opmerkingen
Variants
DANLERS design and manufacture other ControlZAPP High bay mounted variants,
coded by the following order codes:
CZ HB (xx) 10VDC
Suitable for 1-10VDC ballasts
CZ HB (xx) DALI
Suitable for DALI ballasts
Troubleshooting
The load will not switch on:
• The LUX setting as specified by the ControlZAPP App is set too low and is
inhibiting the switch.
• The moving body is not emitting more IR than the background.
(Person wearing insulating clothing in a warm environment)
• Person is too far from the PIR switch, see detection diagram.
• Person is moving unusually slowly (perhaps when testing).
• The control unit battery is not engaged (ON).
Switch RED dip switch next to the telejack connector on the CZ HB (xx)
control unit towards the centre of the control (see diagram E).
The load switches on when nobody is present:
• Heater causing infra-red variations in a small cold room.
Resite the control away from heater.
• Please contact DANLERS for further technical support.
Precautions and Warranty
This product conforms to BS EN 60669-2-1, BS EN 55015 and BS EN 60730.
Please ensure the most recent edition of the appropriate local wiring regulations are observed
and suitable protection is provided (protected with the appropriate MCB) 1kV over voltage.
Please ensure that this device is disconnected from the supply if an insulation test is made.
This product is covered by a warranty which extends to 5 years from the date of manufacture.
Products available from DANLERS
• PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products
Please call for more information or a free catalogue, or visit our website.
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
Web: www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
15/09/16
ControlZAPP high bay passive infra-red occupancy switches can be mounted directly
onto solid ceilings or onto a range of different mounting boxes (diagram A).
ControlZAPP devices incorporate a passive infra-red quad sensor to detect movement
of a warm body within their detection zone (diagram B) and a photocell to monitor the
ambient light level.
ALL adjustments are made via a freely downloadable ControlZAPP App available
from the DANLERS website.
If the ControlZAPP device is set as PIR with LUX input, upon detecting movement, if
the ambient light is dark enough, the ControlZAPP device will turn the load ON. The
ambient threshold can be set to between approximately 30 lux to 1000 lux and infinite
lux (photocell inactive) via the 'Respond to Daylight' settings on the ControlZAPP App.
If no more movement is detected within a pre-selected time as determined by the
ControlZAPP App, then the ControlZAPP device will turn the load off. This 'Time Off
Timeout' or time lag can be set via the ControlZAPP App adjuster between 10sec
and 23hrs 59min 59sec.
These high bay controls are available in three types - each with a particular
detection pattern which is optimised for particular applications.
CZ HB ND:
CZ HB SP:
CZ HB WD:
These controls are suitable for mains switching or DALI switching only.
They can also switch up to:
• 10 amps (3000W) of resistive loads
• 6 amps (1500W) fluorescent lamps, high frequency or switch start,
incandescent or mains halogen lamps (recommended with integral safety fuse)
• 3 amps (750W) of electronic or wire wound transformers.
• 2 amps (500W) of low energy lamps: CFL, LED, 2D etc.
• 1 amp (250W) of fans or most metal halide lamps.
When the control is powered up, it will take 1 minute for the circuitry to stabilise (detection
LED flashing) and ensure the output is off, the ControlZAPP device will then enter its
Default Operating Mode.
Please Note: When in the Default Operating Mode the control is set up as an occupancy
switch with a 20 minute turn OFF timeout (time lag) and photocell disabled.
INS314 CZ HB (xx)
ControlZAPP High bay controls
CZ HB ND
CZ HB SP
CZ HB WD
Narrow Detection version is ideal for covering storage aisles.
Spot Detection version is ideal for smaller areas,
such as the entrances to storage aisles.
Wide Detection version is ideal for large open areas,
such as factories, sports halls and entrance halls.
Loading
Start-up and default settings
Installation notes