Belimo ZIP Economizer Montage-instructies
Blader online of download pdf Montage-instructies voor {categorie_naam} Belimo ZIP Economizer. Belimo ZIP Economizer 2 pagina's. Energy module
Ook voor Belimo ZIP Economizer: Montage-instructie (4 pagina's), Montage-instructies (2 pagina's)
MOUNTING INSTRUCTION
ZIP Economizer
Installation
Each ZIP Economizer module is designed with a unique form fit which allows it
to fit only in one location on the ECON-ZIP-BASE.
Insert the ECON-ZIP-COM module in the far right (designated) slot of the ZIP
Economizer base unit. Illustration located below for location.
Press firmly to lock the module in place – you will hear a snap.
Communication Module
™
Removal of ECON-ZIP-COM
Insert a flat head screw driver into the latch of the module. Apply light
pressure on the latch away from the base unit. Lift up to remove.
ECON-ZIP-COM
Technical Data
Type
Name
Description
Comunication
I/O
Comm
interface
Diagnostic
Relay
ALM
alarm
Electrical Specification
RS485 Interface
Optical Isolation max. 1k VDC
(for max. 1min)
Pin 4: RS485 Com Gnd
Pin 7: RS485 Com A
Pin 8: RS485 Com B
Relay contact 24 V
Normal current: 0.5A
Inrush current: 1A