Datakom DKG-205 Gebruikershandleiding - Pagina 4
Blader online of download pdf Gebruikershandleiding voor {categorie_naam} Datakom DKG-205. Datakom DKG-205 20 pagina's. Automatic mains failure unit
2. INSTALLATION
2.1 Introduction to the Control Panel
The control panel is designed to provide user friendliness for both the installer
and the user. Programming is usually unnecessary, as the factory settings
have been carefully selected to fit most applications. However programmable
parameters allow the complete control over the generating set. Programmed
parameters are stored in a Non Volatile Memory and thus all information is
retained even in the event of complete loss of power.
2.2 Mounting the Unit
The unit is designed for panel mounting. The user should not be able to
access parts of the unit other than the front panel.
Mount the unit on a flat, vertical surface. The unit fits into a standard panel
meter opening of 140x68 millimeters. Before mounting, remove the steel
spring from the unit, and then pass the unit through the mounting opening.
The unit will be maintained in its position by the steel spring.
2.3 Wiring the Unit
WARNING: THE UNIT IS NOT FUSED.
Use external fuses for
Install the fuses as nearly as possible to
the unit in a place easily accessible for the user.
The fuse rating should be 6 Amps.
WARNING: ELECTRICITY CAN KILL
ALWAYS disconnect the power BEFORE
Mains phases: R-S-T
Generator phase: L1-L2-L3
Battery positive: BAT(+).
connecting the unit.
- 4 -