Using the UNI/59

The UNI/59 provides the communications
link between the CMnet and up to 59 T-Line
or U-Line modules. You cannot use a
combination of T-Line and U-Line modules
with the UNI/59. The UNI/59 module can
store one module driver and up to 59 Graphic
Function Blocks (GFBs), depending on the
size of the GFBs.
A UNI/59 module contains a 32-bit
microprocessor, flash memory, and non-
volatile RAM (stores data even during a
power failure) for executing GFBs. The
UNI/59 can communicate with an optional
BACview keypad/display using the Keypad
Display port and can communicate with a
laptop computer running SuperVision using
the UNI/59's Access port and an APT.
You must use a version 6.00g driver or later
with this module. Two module drivers are
available for the UNI/59:
• The U5M module driver (which is the
default driver shipped with the module)
supports only U-Line modules. See the
U5M Module Driver document at
http://www.automatedlogic.com, or
the SupportPlus CD for more
information.
• The U5I module driver (available on the
Automated Logic Corporation web site)
supports only T-Line modules. See the
U5I Module Driver document at
http://www.automatedlogic.com, or
the SupportPlus CD for more
information.
Make sure you use the correct module driver
for your application.
CAUTION Changes or modifications to this
unit not expressly approved by the party
responsible for compliance could void the
user's authority to operate equipment.
Revised 1/3/01 • UNI/59
& ' ( #)#
Figure 1. System Architecture
NOTE This equipment has been tested and
found to comply with the limits for a Class A
digital device, pursuant to Part 15 of the FCC
Rules. These limits are designed to provide
reasonable protection against harmful
interference when the equipment is operated
in a commercial environment. This
equipment generates, uses, and can radiate
radio frequency energy and, if not installed
and used in accordance with the instruction
manual, may cause harmful interference to
radio communications. Operation of this
equipment in a residential area is likely to
cause harmful interference in which case the
user will be required to correct the
interference at his own expense.

Specifications

Power 24VAC ± 10%, 50-60Hz, 0.3A (7.2VA)
power consumption (single Class 2
source only, 100VA or less). (24VAC ±10%,
50-60Hz if ordered for UUKL Smoke
Control Systems.)
Communication One EIA-232 port for
diagnostics (9600 bps or 38.4 kbps), two
EIA-485 ports for Unet communication
(9600 bps or 38.4 kbps), one EIA-485 port
for CMnet communication (9600 bps,
38.4 kbps, or 156 kbps).