HID VertX EVO V1000 Installatiehandleiding - Pagina 8

Blader online of download pdf Installatiehandleiding voor {categorie_naam} HID VertX EVO V1000. HID VertX EVO V1000 19 pagina's.

HID VertX EVO V1000 Installatiehandleiding
VertX EVO V1000 Installation Guide
Input Connections – Input connections are analog inputs used for a combination of specific functions such as
5.
Request-to-Exit (REX), Door monitor, etc. They can also be used as general purpose monitoring. Connect one side
of the switch or contact to the + (plus) lead and the other to the – (minus) lead. The following table shows where the
inputs are located. Pin numbers shown on the cover use the convention +/–.
The default REX input configuration is normally open (NO) unsupervised (no EOL resistors).
However, the default door switch (DS) configuration is Normally Closed (NC), unsupervised (no
EOL resistors).
All other input points are defaulted for NO switches and are unsupervised (no EOL resistors).
Any input can be configured as NO or NC, as well as unsupervised or supervised. They can be configured
for supervisory resistors of 1K – 6K Ohm. The setup of supervised inputs should be done during
configuration of the VertX EVO devices through the host.
Example: Input 1, V1000 is: P14 Pin1 is + and Pin 2 is -.
Except for the door monitor, all other inputs
default to NO, unsupervised:
Input number
1
2
3
4
5
July 2011
V1000
P14 Pins 1/2
P11 Pins 4/3
P7 Pins 8/7 - Tamper
P7 Pins 6/5 - AC Fail
P7 Pins 4/3 - Batt Fail
© 2003 - 2011 HID Global Corporation. All rights reserved.
Supervised inputs can be configured for:
Page 8 of 19