Autonics TCN4M Series Handmatig
Blader online of download pdf Handmatig voor {categorie_naam} Autonics TCN4M Series. Autonics TCN4M Series 2 pagina's. Dual display pid temperature controller
Ook voor Autonics TCN4M Series: Gebruiksaanwijzing (2 pagina's), Handmatig (13 pagina's), Producthandleiding (6 pagina's)
DUAL INDICATOR TEMPERATURE CONTROLLER
TCN4 SERIES
M
A
N
U
A
L
Thank you very much for selecting Autonics products.
For your safety, please read the following before using.
Caution for your safety
Please keep these instructions and review them before using this unit.
Please observe the cautions that follow;
Warning
Serious injury may result if instructions are not followed.
Product may be damaged, or injury may result if instructions are not
Caution
followed.
The following is an explanation of the symbols used in the operation manual.
Caution: Injury or danger may occur under special conditions.
Warning
1. In case of using this unit with machinery (Ex: nuclear power control, medical equipment, ship,
vehicle, train, airplane, combustion apparatus, safety device, crime/disaster prevention
equipment, etc) which may cause damages to human life or property, it is required to install
fail-safe device.
It may cause a fire, human injury or damage to property.
2. Install the unit on a panel.
It may cause electric shock.
3. Do not connect, inspect or repair this unit when power is on.
It may cause electric shock.
4. Wire properly after checking terminal number.
It may cause a fire.
5. Do not disassemble the case. Please contact us if it is required.
It may cause electric shock or a fire.
Caution
1. This unit shall not be used outdoors.
It may shorten the life cycle of the product or cause electric shock.
2
2. When connect wire, AWG 20(0.50mm
) should be used and screw bolt on terminal block with
0.74N.m to 0.90N.m strength.
It may cause a malfunction or fire due to contact failure.
3. Please observe the rated specifications.
It may shorten the life cycle of the product and cause a fire.
4. Do not use beyond of the rated switching capacity of relay contact.
It may cause insulation failure, contact melt, contact failure, relay broken and fire etc.
5. In cleaning unit, do not use water or organic solvent. And use dry cloth.
It may cause electric shock or a fire.
6. Do not use this unit in place where there are flammable or explosive gas, humidity, direct ray
of the light, radiant heat, vibration and impact etc.
It may cause a fire or an explosion.
7. Do not inflow dust or wire dregs into the unit.
It may cause a fire or a malfunction.
8. Please wire properly after checking the terminal polarity when connecting temperature sensor.
It may cause a fire or an explosion.
9. In order to install the units with reinforced insulation, use the power supply unit which basic
insulation level is ensured.
Ordering information
T
CN
4 S
2 4 R
Control output
Relay contact output + SSRP output (AC power)
R
Relay contact output + SSR output (AC/DC power)
Power supply
24VAC 50/60Hz, 24-48VDC
2
100-240VAC 50/60Hz
4
Sub output
Alarm1 + Alarm2 output
2
DIN W48 X H48mm
S
Size
DIN W72 X H72mm
M
DIN W48 X H96mm
H
DIN W96 X H96mm
L
Digit
4Digit(9999)
4
Setting type
Dual display type, set by touch switch
CN
Item
Temperature controller
T
The above specifications are subject to change without notice.
Specifi cation
Series
TCN4S
TCN4M
TCN4H
100-240VAC 50/60Hz
Power
AC Power
supply
24VAC 50/60Hz, 24-48VDC
AC/DC Power
Allowable voltage range
90 to 110% of rated voltage
Max. 5VA(100-240VAC 50/60Hz, 24VAC 50/60Hz)
Power consumption
Max. 3W(24-48VDC)
Display method
7 Segment LED(PV: Red, SV: Green)
PV(WXH) 7.0 X 15.0mm
9.5 X 20.0mm
7.0 X 14.6mm
Character
size
SV(WXH) 5.0 X 9.5mm
7.5 X 15.0mm
6.0 X 12.0mm
RTD
DIN Pt100Ω, Cu50Ω (Allowable line resistance max.5Ω per a wire)
Input
type
TC
K(CA), J(IC), L(IC), T(CC), R(PR), S(PR)
RTD
Based on room temperature (23ºC ± 5ºC): (PV ± 0.5% or ±1ºC higher one) rdg ± 1 Digit
Display
accuracy
1
TC
In case of out of room temperature range: (PV ± 0.5% or ±2ºC higher one) rdg ± 1Digit
Relay
250VAC 3A 1a
Control
output
SSR
12VDC±2V 20mA Max.
Alarm output
AL1, AL2 Relay: 250VAC 1A 1a
Control method
ON/OFF control, P, PI, PD, PID control
Hysteresis
1 to 100
/0.1 to 50.0
ºC
ºC
Proportional band(P) 0.1 to 999.9
ºC
Integral time(I)
0 to 9999 sec.
Derivative time(D)
0 to 9999 sec.
Control period(T)
0.5 to 120.0 sec.
Manual reset
0.0 to 100.0%
Sampling period
100ms
AC power
2000VAC 50/60Hz 1min.(Between input terminal and power terminal)
Dielectric
strength
AC/DC power
1000VAC 50/60Hz 1min.(Between input terminal and power terminal)
Vibration
0.75mm amplitude at frequency of 5 to 55Hz in each X, Y, Z directions for 2 hours
Relay life
Control output Mechanical: Min. 5,000,000 operations, Electrical: Min. 200,000 operations (250VAC 3A resistive load)
cycle
Alarm output
Mechanical: Min. 5,000,000 operations, Electrical: Min. 300,000 operations (250VAC 1A resistive load)
Insulation resistance Min. 100MΩ(at 500VDC megger)
Noise immunity
Square-wave noise by noise simulator(pulse width 1㎲)
±
2KV R-phase and S-phase
Memory retention
Approx. 10 years (When using non-volatile semiconductor memory type)
Ambient
-10 to 50
ºC
, Storage: -20 to 60
ºC
Environ
Temperature
-ment
Ambient
35 to 85%RH, Storage: 35 to 85%RH
humidity
Unit weight
Approx. 100g
Approx. 133g
Approx. 124g
1: For display accuracy
- In case of room temperature (23ºC ± 5ºC)
Below 200ºC of thermocouple R, S is PV ± 0.5% or ±3ºC higher one ± 1 digit
Over 200ºC of thermocouple R, S is PV ± 0.5% or ±2ºC higher one ± 1 digit
Termocouple L (IC), RTD CU50Ω is PV ± 0.5% or ±2ºC higher one ± 1 digit
- In case of out of room temperature range
Below 200ºC of thermocouple R, S is PV ± 1.0% or ±6ºC higher one ± 1 digit
Over 200ºC of thermocouple R, S is PV ± 0.5% or ±5ºC higher one ± 1 digit
RTD CU50Ω is PV ± 0.5% or ±3ºC higher one ± 1 digit
Environment resistance is rated at no freezing or condensation.
Parts description
1. Present temperature (PV) display (Red)
1) RUN mode: Present temperature (PV) display
2) Parameter setting mode: Parameter display
1
2. Set temperature (SV) display (Green)
1) RUN mode: Set temperature (SV) display
2) Parameter setting mode: Parameter setting value display
8
3. Control/Alarm output display lamp
3
1) AL1/AL2: When AL1, AL2 alarm output ON, this lamp
2
turns ON.
2) OUT: When control output ON, this lamp turns ON.
7
4
During SSRP control output type in CYCLE/PHASE
5
control, this lamp turns ON when MV is over 3.0%.
4. Auto tuning lamp
AT lamp flashes by every 1 sec during operating auto tuning.
5.
MODE
key
6
Used when entering into parameter setting group, returning
to RUN mode, moving parameter, and saving setting values.
6. Adjustment
Used when entering into set value change mode, digit
moving and digit up/down.
7. Digital input key
Press
keys for 3 sec. to operate the set function
(RUN/STOP, alarm output reset, auto tuning) in digital input
key [DI-T].
ºC
8. Temperature unit (
/℉) indicator
It shows current temperature unit.
Input sensor and temperature range
Input sensor
Display
Temperature range(
ºC
)
Temperature range(℉)
-50 to 1200
KCaH
K(CA)
KCaL
-50.0 to 999.9
-58.0 to 999.9
JIcH
-30 to 800
J(IC)
JIcL
-30.0 to 800.0
-22.0 to 999.9
LIcH
-40 to 800
Thermorcouple
L(IC)
LIcL
-40.0 to 800.0
TCcH
-50 to 400
T(CC)
TCcL
-50.0 to 400.0
-58.0 to 752.0
R(PR)
RPR
0 to 1700
S(PR)
SPR
0 to 1700
DPtH
-100 to 400
-148 to 752
DPt100Ω
DPtL
-100.0 to 400.0
-148.0 to 752.0
RTD
CUsH
-50 to 200
CU50Ω
CUsL
-50.0 to 200.0
-58.0 to 392.0
Dimensions
TCN4L
1)TCN4S
11.0 X 22.0mm
7.0 X 14.0mm
2)TCN4M
3)TCN4H
Approx. 179g
4)TCN4L
5)Terminal cover(Sold separately)
6)Panel cut-out
A
D
Unit
A
Model
TCN4S
Min. 65
B
C
TCN4M
Min. 90
TCN4H
Min. 65
TCN4L
Min. 115
-58 to 2192
Installation
TCN4S(48X48mm) series
Other series
-22 to 1472
-40 to 1472
-40 to 999.9
-58 to 752
32 to 3092
32 to 3092
-58 to 392
Insert product into a panel, fasten bracket by pushing with tools as shown above.
[Unit: mm]
Connections
1)TCN4S
Terminal
cover
-
+
Terminal
cover
Terminal
cover
-
+
Terminal
cover
Flow chart for setting group
1. All Parameter
Run mode
Please any key among
2sec.
MODE
,
,
,
MODE
SV setting
Parameter 1group
PAR1
AL1 alarm termerature
AL1
AL2 alarm termerature
AL2
Auto tunung
AT
Proportional band
P
Integral time
I
B
C
D
Derivative time
Min. 65
45
+0.6
45
-0
D
Min. 90
68
+0.7
68
+0.7
-0
-0
Min. 115
45
92
+0.8
Manual reset
-0
Min. 115
92
92
+0.8
+0.8
REST
-0
-0
Hysteresis
HYS
3sec.
MODE
Press
key over 3 sec in any setting group, it saves the set value and returns to RUN mode.
MODE
(Exception: Press
key once in SV setting group, it returns to RUN mode).
MODE
If no key entered for 30 sec., it returns to RUN mode automatically and the set value of parameter is
not be saved.
Press
key again within 1 sec. after returning to RUN mode, it advances of the fi rst parameter of
MODE
previous setting group.
Press
key to move next parameter.
MODE
Parameter marked in
might not be displayed depending on other parameter settings.
Set parameter as 'Parameter 2group → Parameter 1group → Setting group of set value' order
considering parameter relation of each setting group.
1: It is not displayed for AC/DC power model (TCN4 -22R).
2)TCN4M
B' RTD TC
-
B
+
A
B' RTD TC
-
B
+
-
A
+
※2
SOURCE
1: 12VDC±2V 20mA Max.
2: AC power: 100-240VAC 5VA 50/60Hz
AC/DC power: 24VAC 5VA 50/60Hz
24-48VDC 3W
4sec.
MODE
Parameter 2group
PAR2
Input
Temperature
Input
Input
sensor
unit
correction
digital fi lter
IN-T
UNIT
IN-B
MAvF
Control output
SV high-
SV low-limit
Control type
operation
limit value
value
C-MD
O-FT
H-SV
L-SV
Control output
SSRP output
Control
AL1 alarm
※1
type
method
cycle
operation mode
OUT
SSrM
T
AL-1
LBA
Alarm output
AL2 alarm
LBA detection
monitoring time
hysteresis
operation mode
band
LBaT
AHYS
AL-2
LBaB
Digital input
Control output MV in case
key
of input break error
Lock setting
DI-K
ErMV
LOC
3sec.
MODE