AGS Parksafe Control Panel Installatie-, bedienings- en onderhoudshandleiding - Pagina 15
Blader online of download pdf Installatie-, bedienings- en onderhoudshandleiding voor {categorie_naam} AGS Parksafe Control Panel. AGS Parksafe Control Panel 20 pagina's. Ventilation control panel
Ook voor AGS Parksafe Control Panel: Installatie- en bedieningshandleiding (16 pagina's), Installatie- en bedieningshandleiding (16 pagina's), Installatie, bediening en onderhoud (16 pagina's)
Installation, Operation & Maintenance
Step 2. Test Detector
Access to the interior of the detector, when carrying out any work, must be conducted by a competent person!
Apply a gas concentration ~50% higher than the alarm setpoint but do not exceed the upper limit of measurement!
Ensure you have the correct calibration gas for the device type.
•
If using a cylinder - screw the regulator/valve into the gas cylinder outlet.
•
Offer up the applicator hose/cone and fully cover the sensing element on the front case.
•
Open the valve/regulator to allow the gas to be delivered at a pre-set flow rate.
•
Apply gas to the gas inlet holes on the front of the detector housing.
•
The detector 'Alarm' LED will illuminate at the alarm set point.
•
The Controller will activate all configured outputs/relays (unless service mode is activated) and will display the gas
•
concentration detected.
Remove applicator hose/ cone and turn the gas cylinder regulator/valve off.
•
Wait for detector to stabilise / return to normal.
•
Reset the service reminder by tapping the circuit test button 3 times (within 2 seconds)
•
Test complete.
•
Record your test details.
•
Rev: 20
ParkSafe Controller
15