Dea 124RR Instructies en waarschuwingen - Pagina 5

Blader online of download pdf Instructies en waarschuwingen voor {categorie_naam} Dea 124RR. Dea 124RR 11 pagina's. Control board 24v for gate automation operating

Dea 124RR Instructies en waarschuwingen
Operating instructions and warnings
By pressing on the "OK" key when the control board awaits further instructions ("----"), the display shows
some vertical segments: each one of them is associated to one of the control board inputs (see the picture
above). When the segment is lighted it means that the contact associated to it is closed, on the contrary,
when it is switched off the contact is open. You can now position the door/gate in its position of max.
opening. In order to do this:
8.2
Setup and memorization of motor stroke
WARNING During motors stroke memorisation, the control board detects automatically the presence
and type of photocells, safety devices and limit switches which are installed. It is therefore essential that
during this phase the latter be properly connected and working.
Instructions
The control board is ready to receive instructions
Scroll down the parameters until you visualize procedure P001
Confirm! The control board is ready for the positioning of the door/gate
Position the door/gate in its standstill position while opening
Confirm! The control board has memorized the door/gate position
Scroll down the parameters until you visualize procedure P003
Confirm! The control board awaits a further confirmation
Confirm by pressing on the OK key for a few seconds! The procedure starts
Now the door/gate starts to close in the slow down phase until it
reaches the stroke end while closing (or the limit switch).
On the display you will read "P003". Motor stroke memorization done!
Scroll down the parameters until "----". The control board awaits further instructions
1
By pressing on the
happen, you must swap the two motor cables (terminals 7 and 9) Only if you use limit switches, first position the door/gate
where you want it to stop in closing and then adjust the closing cam so that it presses on the limit switch associated to it in
that point. Then position the door/gate in the opening position and adjust the opening cam so that it presses on the limit
switch associated to it in that point.
8.3

Built-in radio receiver

DEA 124RR control board includes a 433,92MHz built-in radio receiver accepting both transmitters with
16
HCS coding (complete rolling code or just fixed part), and HT12E dip-switch coding.
•The type of coding is selected by programming the working parameter n° 8 "type of coding" (see Table
2 Parameters)
•The receiver memory capacity can contain up to 100 different transmitters.
•When receiving a pulse from the transmitter, depending on your channel selection and linking, the start
or the pedestrian inputs are activated. In fact, by programming one of the working parameters it is
possible to choose, according to one's needs, which key of the memorized transmitters will activate the
start input and which one will activate the pedestrian input (see "4. Channel selection and linking on
the transmitter").
•While you memorize each transmitter the display shows a progressive number by which you will be able
to trace and, if necessary, delete each transmitter individually
R
Door/gate positioning
Motors stroke memorization
key the door/gate must open, by pressing on the
Function
key the door/gate must close. If this does not
Display
1
A7