Dell S6010-ON Installatiehandleiding - Pagina 33
Blader online of download pdf Installatiehandleiding voor {categorie_naam} Dell S6010-ON. Dell S6010-ON 46 pagina's.
Ook voor Dell S6010-ON: Opmerkingen over firmware-uitgave (12 pagina's)
The S6010–ON comes from the factory with two PSUs and five fan modules installed in the chassis. The fan modules and the integrated
fan-power supply are hot-swappable.
NOTE:
To run the system, both slots must have operating fan units. If you do not install a module in each slot, either as part of
the PSU or as an independent fan module, the system shuts down in one minute.
In addition to the integrated fan/power supply modules, you can order and install fan modules separately.
The system supports two airflow direction options. Do not mix airflow types in a chassis; you can use only a single airflow direction in a
chassis. If you mismatch the airflow directions, the system powers down in one minute.
•
Normal—airflow is from the I/O side to the PSU side.
•
Reversed—airflow is from the PSU side to the I/O side.
All fans and PSUs in a configuration must be in the same airflow direction.
Environmental factors can decrease the amount of time required between fan replacements. Check the environmental factors regularly. An
increase in temperature and/or particulate matter in the air might affect performance; for example, new equipment installation.
CAUTION:
Check the fans at six-month intervals and replace them as necessary. To accurately determine replacement intervals,
regularly monitor the speeds of the cooling fans.
Topics:
•
Components
•
Fan module installation
•
Fan module replacement
•
Fan air filter replacement
Components
The following list the fan components:
•
S6010–ON AC power supply with integrated fan module
•
S6010–ON AC power supply with integrated fan module—Reverse flow
•
S6010–ON DC power supply with integrated fan module
•
S6010–ON DC power supply with integrated fan module—Reverse flow
7
Fans
Fans
33