Chromalox WT-122 Installatie-instructies - Pagina 2
Blader online of download pdf Installatie-instructies voor {categorie_naam} Chromalox WT-122. Chromalox WT-122 4 pagina's. Type wt room thermostat
Ook voor Chromalox WT-122: Installatie-instructies (2 pagina's)
Temp.
Range
Model
(˚F)
Contacts
WT-121
45-75
SPST
WT-122
45-75
DPST
General
Note: Type WT thermostats are designed for temperature
control service only. Because they do not fail safe, they
should not be used for temperature limiting duty.
Users should install adequate back-up controls and
safety devices with their electric heating equipment.
Where the consequences of failure may be severe,
back-up controls are essential. Although the safety
of the installation is the responsibility of the user,
Chromalox will be glad to make equipment recom-
mendations.
Not for use in hazardous environments as described
in the National Electrical Code. Failure to comply
can result in explosion or fire.
Installation
1. Cut lead wires protruding from outlet box approximately
4" from wall surface and strip end insulation 1/2".
2. Always test the heater circuit for electrical shorts before
connecting the thermostat.
3. Remove thermostat knob and front cover.
4. Using wire-nuts or other local code approved devices,
connect load and line wires to appropriate color coded
thermostat wires. (See wiring diagrams below.)
2.86"
(73)
4.72"
(110)
Front View
24V AC
120V AC
22 amps or
22 amps or
528 total
2640 total
watts
watts
2
2.14"
(54)
Side View
Maximum Rating
208V AC
240V AC
22 amps or
22 amps or
4575 total
5280 total
watts
watts
Thermostat Location
1. Mount in any standard electrical outlet box. Use of extra
deep box (3" x 2" x 31/2") makes for easier wiring.
2. Locate outlet box about 5' above floor on inside wall.
3. Box location should be representative of the area to be
controlled. Avoid locations that are subject to drafts or
false external heat (such as solar radiation, direct heat
from heaters, etc.). Insure that the wall selected is capped
to prevent drafts within the wall.
5. Mount the thermostat to the outlet box using the screws
provided. Take care not to push or damage the bimetal
sensing element during installation.
6. Replace the thermostat front cover and knob.
Any knob temperature setting below 50°F may re-
sult in freezing.
277V AC
Pilot Duty
18 amps or
125V AC (use with
5000 total
AC contactor)
watts