Chromalox WT-122 Installatie-instructies - Pagina 3
Blader online of download pdf Installatie-instructies voor {categorie_naam} Chromalox WT-122. Chromalox WT-122 4 pagina's. Type wt room thermostat
Ook voor Chromalox WT-122: Installatie-instructies (2 pagina's)
Wiring
Hazard of Electric Shock. Disconnect all power be-
fore wiring or servicing this control.
Electric wiring to heater must be installed in accordance with
National Electrical Code and with local codes.
Use copper conductors only.
Figure 1
Note:
1. Connect anticipator lead (white) in parallel with heater.
2. Thermostat performance will be degraded if anticipator con-
nection is omitted.
Connect wires according to wiring diagrams (Figures 1 & 2).
Note: Electrical connections should be made with generous
loops of wire — approximately 6" per lead.
Note: If load amperage or voltage rating exceeds switch rat-
ing, a contactor must be used.
Figure 2
Note:
1. Suitable for control of one heating load only.
2. No separate connection required for heat anticipation.
3. Temperature control switch is located on right hand side when
thermostat is viewed from the rear.
3