9.3
Example for signal input / output
(conventional analogue / binary control)
Procede as follows to switch the actuator into automatic mode (AUT):
- activate digital inputs D1, D2, and D3 using the configuration software (standard configuration with
default factory settings).
- activate the AUT mode using the configuration software (standard configuration with default factory
settings).
9.3.1
Standard wiring (analogue setpoint)
+ Y
1
2
3
+ -
+ -
Fig. 10:
9.3.2
Behind a step controller
(binary control without an analogue setpoint)
Contrac actuators feature smooth and continous operation even if the elctronic unit receives binary
commands from a step controller. Use the configuration software for the appropriate settings. The elec-
tronic unit will then integrate the step commands and internally generate an analogue setpoint signal.
.
+ Y
1
2
+ -
Fig. 11:
9.4
Connecting the cable shield
Fig. 12: Connecting the cable shield of EAN823; EBN853; EBN861
Connect the screen at the actuator accordingly.
12
AUT
MAN
- Y
5
8
9 10
11
4
6
7
+ -
- Y
5
3
6
8
9 10
4
7
+ -
+ -
3
1
4
26
27
12
13
14
15
+ -
-
+
RB
24V
+ -
26
27
11
12
13
14
15
+ -
-
+
RB
24V
+ -
4
3
2
1
r00331x1
28
29
30
31
+
-
RB
+
I
+ -
Uv
U
24V
28
29
30
31
+
-
RB
+
I
+ -
Uv
U
24V
- Remove approximately 2 cm of the
cable sheathing (1) at the cable entry
of the housing (4).
- Open the cable shield in this area
and fold it back over the cable
sheathing (1).
- Insert the cable end in the cable entry
and fasten it with the clamp; make
sure that the shield is folded back
and in contact with the clamp and
the electronics housing.
r00358x1
r00359x1