CLW-SW, SWS, & SLVS(W/A/B)
section breaks off from the mounting plate. Use a
file or sandpaper to remove any excess metal.
Prewire for Master Application
Each device has two Class 2 low voltage wires (plus a
ground wire) that provide a Cresnet connection over
shielded twisted-pair to a Crestron control system. These
wires are routed to the bottom of the device for
connection outside of the wallbox. The low voltage wires
are pulled from each device location to the control
system, a Crestron power supply, a Crestron C2N-NPA8
Poll Accelerator, or a Crestron connection block device.
Use # 22 AWG, twisted, shielded, 2-conductor wire.
Wiring can be daisy chained, T-tapped, or home run back
to the control system. Refer to the following wiring
diagram.
Wiring Diagram of CLW device to Cresnet
NOTE: The GRAY (Cresnet) wires are not polarized.
These wires can be connected to either the Y or Z line on
a Cresnet port.
NOTE: The BLACK wire (Cresnet ground) should not
be grounded with the GREEN (Ground) wire on the
-SW/-SWS/-SLVS.
NOTE: Crestron recommends using Crestron's Cresnet-
DM cable for connecting the -DIM and -DIMS to the
Cresnet network.

Installation

NOTE: The -SWS must be installed in the same wallbox
that contains the connections to the load.
NOTE: The -SW, -SWS require a neutral wire for
operation. If no neutral is present, contact a licensed
electrician for installation.
WARNING: Turn off power at the circuit breaker.
Installing with power on can result in serious personal
injury and damage to the device.
4 • Stand Alone Wall Box Switch : CLW-SW, SWS, & SLVS
NOTE: New installations should be checked for short
circuits prior to installing the -SW, -SWS, or -SLVS.
With power off, close the circuit and restore power. If the
load does not work or a breaker trips, check and correct
the wiring or fixture (if necessary). Install the -SW,
-SWS, or -SLVS only when the short is no longer present.
The warranty is void if the -SW, -SWS, or -SLVS is
installed and operated with a shorted load.
1. Turn power off at the circuit breaker.
2. If installing multiple switches (-SW or -SWS),
note the serial number on each device and make
sure they are being installed in the proper
location.
3. Pull Class 2 low voltage wires through a hole in
the drywall located outside of the electrical box,
to the Crestron control system, a Crestron power
supply, a Crestron C2N-NPA8, or a Crestron
connection block device. Leave wires outside of
the wallbox for connection to the -SW or -SWS.
NOTE: Alternate wiring methods may be used for the
Class 2 wiring connections. Refer to section 725-55, Part
D of the 2002 National Electric Code.
4. Wire the device for the appropriate application.
Choose either "CLW-SW / CLW-SWS Wiring"
or "CLW-SWS with CLW-SLVS Wiring",
shown on this page and the following page.
CLW-SW / CLW-SWS Wiring
NOTE: The -SW and -SWS require a neutral wire for
operation. If no neutral is present, contact a licensed
electrician for installation.
The following wiring diagram illustrates installation of
the -SW or -SWS.
Wiring Diagram for CLW-SW or CLW-SWS (without CLW-
SLVS)
Hot
BLUE
(-SWS ONLY)
BLACK
RED
LINE
120VAC
60Hz
WHITE
GREEN
Ground
Cresnet
Neutral
Installation Guide – DOC. 6134B
Load