Crestron CLW-SLVS Gebruikershandleiding - Pagina 5

Blader online of download pdf Gebruikershandleiding voor {categorie_naam} Crestron CLW-SLVS. Crestron CLW-SLVS 6 pagina's. Stand-alone wall box switch

NOTE: The RED (Load) and BLACK (Hot) wires are
#14 AWG. The BLUE (Slave) and WHITE (Neutral)
wires are #18 AWG. The GREEN (Ground) wire is #16
AWG. The GRAY (Cresnet) wires are #22 AWG. The
BLACK wire (Cresnet ground) paired with the GRAY
(Cresnet) wires is #22 AWG.
CLW-SWS with CLW-SLVS Wiring
NOTE: The -SWS must be installed in the same wallbox
that contains the connections to the load.
The following wiring diagram illustrates installation of
the -SWS with a -SLVS.
Wiring Diagram of CLW-SWS with CLW-SLVS
CLW-SLVS
CLW-SLVS
Hot
BLACK
BLUE
BLACK
LINE
120VAC
60Hz
WHITE
GREEN
WHITE
Ground
Neutral
NOTE: Do not connect the BLUE (Slave) wire to the
BLACK (Hot) or RED (Load) wires.
NOTE: The RED (Load) and BLACK (Hot) wires are
#14 AWG. The BLUE (Slave) and WHITE (Neutral)
wires are #18 AWG. The GREEN (Ground) wire is #16
AWG. The GRAY (Cresnet) wires are #22 AWG. The
BLACK wire (Cresnet ground) paired with the GRAY
(Cresnet) wires is #22 AWG.
NOTE: If a -SWS is installed without a -SLVS, the
BLUE lead (Slave) should be capped.
NOTE: The WHITE (Neutral) connection on the -SLVS
is optional and is only required for operation of the LED.
If the neutral is not available, the white lead should be
capped off.
5. Splice the gray wires of the -SW or -SWS to the
Class 2 low voltage wires connected to the
Crestron control system, a Crestron power
supply, or a Crestron connection block device.
Push the wires and the splices into a hole in the
drywall to provide the necessary separation.
6. Push all Class 1 Power wires back into the
wallbox and fasten the device to the wallbox
with the provided screws.
Installation Guide – DOC. 6134B
CLW-SWS
BLUE
BLUE
BLACK
RED
GREEN
WHITE
GREEN
Ground
Ground
Cresnet
CLW-SW, SWS, & SLVS(W/A/B)
7. Attach decorative faceplate.
8. Restore power.
Operating Buttons and Switches
The -SW, -SWS, and -SLVS feature two pushbuttons (one
large, and one small). The -SW and -SWS also have a
three-position mode selection switch. The function of
each button is determined by the position of the mode
selection switch. Refer to the diagram below for the
location of the buttons and the switch.
Buttons of CLW-SW, -SWS, and -SLVS
Load
NOTE: The -SLVS does not have a mode selection
switch. It will act in the same mode as the -SWS.
OFF
When the mode selection switch is in the "OFF" position,
the buttons will not have any function and the load is
disconnected from the power source. This must be used
when changing light bulbs to ensure that the load is fully
disconnected from power.
ADJ
When the switch is in the ADJ position, the load can be
manually activated and deactivated by pressing the large
button. Pressing and holding the small button will set a
delay time for deactivating the load when the switch is in
the PRE position. To set the delay time, press and hold
the small button for the desired amount of time delay and
release the button. When the small button is released, the
LED will flash three times to confirm the time delay
setting. When done, return the switch to the PRE position.
NOTE: If a time delay is not set, the factory default is 10
seconds.
Stand Alone Wall Box Switch: CLW-SW, SWS, & SLVS • 5
Large Button
Small Button
Mode Selection Switch
(-SW & -SWS Only)