Ook voor Siemens SIMATIC ET 200S: Gebruikershandleiding (18 pagina's), Handmatig (16 pagina's), Gebruikershandleiding (16 pagina's), Gebruikershandleiding (26 pagina's), Handmatig (37 pagina's), Handmatig (24 pagina's), Functiehandboek (40 pagina's), Gebruiksaanwijzing (4 pagina's), Originele gebruiksaanwijzing (19 pagina's), Originele gebruiksaanwijzing (20 pagina's), Handmatig (34 pagina's), Handmatig (14 pagina's), Handmatig (24 pagina's), Originele gebruiksaanwijzing (17 pagina's), Originele gebruiksaanwijzing (19 pagina's), Handmatig (16 pagina's), Handmatig (12 pagina's), Handmatig (32 pagina's), Handmatig (18 pagina's), Handmatig (12 pagina's), Handmatig (28 pagina's), Handmatig (22 pagina's), Handmatig (22 pagina's), Handmatig (36 pagina's), Handmatig (16 pagina's)

Siemens SIMATIC ET 200S Handmatig
Connecting

5.2 Wiring unused channels of the analog input modules

Sensor selection
Note the following factors when selecting the sensors:
● Length, impedance, and capacitance of the cable
● Reaction speed of the utilized sensors
5.2
Wiring unused channels of the analog input modules
Rules
Pay attention to the following instructions when wiring unused channels:
● "Deactivate" unused input channels when assigning parameters.
● A deactivated channel always returns the value 7FFF
● The cycle time remains unchanged at 250 µs.
5.3

Using the shield connection

Rules
To prevent interference we recommend the following for analog electronic modules:
● Use shielded wires to the sensors and actuators.
● Lay out the wire shields on the shield connection.
● Connect the shield connection to the ground bus with low impedance.
Note
The permitted limit values can be exceeded (up to <10%) at the measuring inputs of the
electronic module in the event of cable-related HF radiation up to 100 kHz. This is made
necessary by the specified measuring procedure.
26
.
H
2AI I 4WIRE HS analog electronic module (6ES7134-4GB62-0AB0)
Manual, 01/2008, A5E01076124-02