Function Introduction
Cooling Mode
1.
When PV(Current Temperature) ≥ Csp(Cooling Start Point), the temperature controller enter
cooling mode. The LCD will show
closed, then the cooling socket will output voltage, and the cooling equipment start working.
When LED and
status. When PV≤SP,
opened, and the cooling equipment stop working.
Eg
Setting SV=25°C, CD=2°C, HD=30 so Csp=SV+CD=27r, Hsp=SV-HD=22-C. When
:
current temperature PVS≥27℃ (Csp), the temperature controller enter cooling mode, and the
cooling equipment start working. When the temperature is less than 25℃ (SV) , it stops cooling.
In addition, when current temperature PV≤22℃(Hsp) , it enters heating mode. When the
temperature is more than 25℃ (SV) , it stops heating.
Heating Mode
2.
When PV(Current Temperature) ≤ Hsp(Heating Start Point), the temperature controller enter
heating mode. The LCD will show
dosed, then the heating socket will output voltage, and the heating equipment start working.
When PV≥SP,
on LCD will disappear, the heating LED lights out, the heating relay is opened,
and the heating equipment stop working.
,the cooling LED is light on the panel, the cooling relay is
flash, it means the cooling equipment enter compressor delay protection
on LCD will disappear, the cooling LED lights out, the cooling relay is
,the heating LED is light on the panel, the heating relay is
- 5 -