Programming
6
The FP-08450 Control Panel provides several programming options,
allowing it to be adapted to site conditions. The 2-way DIP switches
inside the panel next to the terminal block allow one of 4 modes to
be selected. To access the DIP switches, open the panel enclosure.
Note: All programmed settings should be recorded in the logbook.
Switch 1
Note: If a Discharge Delay Module (P/N FP-08850) is installed, panel must be programmed
for extended discharge.
Operation
7
LED Indicators
7.1
The FP-08450 Control Panel uses LED indicators to notify the operator
of the condition of the control panel and each of the monitored circuits.
If an LED is illuminated, it indicates the following:
Circuit
Power
Circuit 1 Alarm
Circuit 2 Alarm
Fault
Isolated
Discharging
Isolate Function
7.2
To isolate the control panel, press and hold Mode Switch 1 until a 1 beep is heard and the
"Isolated" LED is illuminated.
To restore the control panel to normal operation, press Mode Switch 1 and ensure the
"Isolated" LED turns off.
Isolating disables automatic activation. Manual Activation will remain operational.
When isolated, the control panel continues to monitor for alarm and fault, and show the alarm
and fault indications, but will not operate the siren and the automatic discharge. When
isolated, any change in the detector status, will cause the panel sounder to operate for 1
second as an alert of the status change, but the panel will remain isolated.
The isolate function will also silence the siren/strobe and the internal sounder but will not
cancel the alarm or fault indication.
Mode
Standard Discharge
Power Applied for 2
OFF
seconds
DEFAULT
Extended Discharge
ON
Power applied for 240
seconds
LED
Power supply is available
System is in alarm condition
System is in alarm condition
System is in fault condition and needs servcing
System has been isolated using buttons on panel
System has initiated activation sequence
Switch 2
Condition
Mode
Manual Discharge
OFF
Detectors operate
siren/strobe only
Automatic Discharge
Detection on Circuit 1
ON
Alarm will discharge
system
DEFAULT
Page | 13