04 Compressor Minimum Off Time
Factory Default: 2 Minutes. Range: 0 to 9 Minutes
Touch the
UP/DOWN
keys to
change the minimum off time
(minutes) before restarting the
compressor.
Touch
NEXT
to display the
next option, or
ENTER
to save
the option and return to normal
thermostat operation.
05 Heating Minimum Off Time
Factory Default: 0 Minutes. Range: 0 to 9 Minutes
Touch the
UP/DOWN
keys to
change the minimum off time
(minutes) before restarting a
gas furnace or electric strip
heater.
Touch
NEXT
to display the
next option, or
ENTER
to save
the option and return to normal
thermostat operation.
06 Minimum Run Time
Factory Default: 2 Minutes. Range: 0 to 9 Minutes
Touch the
UP/DOWN
keys to
change the minimum run time
(minutes) before turning a
system off.
Touch
NEXT
to display the
next option, or
ENTER
to save
the option and return to normal
thermostat operation.
07 Setting On-Off Temp Differential
Factory Default: #1. Range: 0, 1 or 2.
Touch the
UP/DOWN
keys to
select 0, 1, 2.
Touch
NEXT
to display the
next option, or
ENTER
to save
the option and return to normal
thermostat operation, or touch
the hidden
BACK
key to return
to the previous option.
o
0
Turns cooling On 1 above setpoint and Off at Setpoint.
o
Turns heating On 1 below setpoint and Off at Setpoint.
o
1
Turns cooling On 1 above setpoint, Off .5 below Setpoint.
o
Turns heating On 1 below setpoint, Off .5 above Setpoint.
o
2
Turns cooling On 1 above setpoint, Off 1 below Setpoint.
o
Turns heating On 1 below setpoint, Off 1 above Setpoint
08 Smart Recovery
Factory Default: Off. Range: On or Off.
Smart recovery initiates a heating or cooling call so that the space is
at temperature when the setback period ends.
Touch the
UP
key to select ON
to turn on smart recovery or
touch the
DOWN
key to select
OF to turn smart recovery off.
Touch
NEXT
to display the
next option, or
ENTER
to save
the option and return to normal
thermostat operation.
Touch the
select the heating temperature
Option
when the space is vacant.
Touch
next option, or
the option and return to normal
thermostat operation, or touch
NEXT
ENTER
the hidden
to the previous option.
Touch the
Option
select the cooling temperature
when the space is vacant.
Touch
next option, or
the option and return to normal
NEXT
ENTER
thermostat operation, or touch
the hidden
to the previous option.
Touch the
Option
change the downstairs (Inside)
temperature to the temperature
that the user feels is correct.
Touch
next option, or
NEXT
ENTER
the option and return to normal
thermostat operation, or touch
the hidden
to the previous option.
Option
Touch the UP/DOWN keys to
change the upstairs (Inside2)
temperature to the temperature
that the user feels is correct.
Touch NEXT to display the
NEXT
ENTER
next option, or ENTER to save
the option and return to normal
thermostat operation, or touch
the hidden BACK key to return
o
o
to the previous option.
o
o
.
This is the frequency, in minutes, that the damper position is updated.
Touch the
set the time in minutes to
update the upstairs and
downstairs airflow.
Option
Touch
next option, or
the option and return to normal
thermostat operation, or touch
the hidden
NEXT
ENTER
to the previous option.
6
09 Vacant Heating Setpoint
o
Factory Default: 65 F.
Range: 44 F to 75 F
UP/DOWN
keys to
NEXT
to display the
ENTER
to save
BACK
key to return
10 Vacant Cooling Setpoint
o
Factory Default: 80 F.
Range: 74 F to 95 F
UP/DOWN
keys to
NEXT
to display the
ENTER
to save
BACK
key to return
11 Calibrate Downstairs Temperature Sensor
Factory Default: None.
Range - +/-5
UP/DOWN
keys to
NEXT
to display the
ENTER
to save
BACK
key to return
12 Calibrate Upstairs Temperature Sensor
Factory Default: None.
Range - +/-5
13 Airflow Update Time
Factory Default: 2 Minutes. Range: 1 to 20 Minutes.
UP/DOWN
keys to
NEXT
to display the
ENTER
to save
BACK
key to return
o
o
Option
Heat
Vacant
NEXT
ENTER
o
o
Option
Cool
Vacant
NEXT
ENTER
o
Option
Inside
NEXT
ENTER
o
Option
Inside2
NEXT
ENTER
Option
NEXT