Please consider:
With a condensation dryer a relative humidity of minimum 40 – 45% r.h. are
possible. If you need lower values, you should use an adsorption dryer. Please
contact your dealer!
Agreeable climate:
For living areas a climate of 20 – 25° C and 50 – 60% r.H. is
While drying or storaging rooms with wood furnishing, the humidity should
not fall below 55 – 60% r.H.
For unclear drying request, please contact your dealer.
5.5 Condensate outlet
The dehumidifier AD 110 is with 3 mtr. Run off hose (12 mm)
The end of the hose must be situated lower than the beginning of the hose (runoff
socket)!
The hose must never be bent!
No objects must be placed onto the hose!
ATTENTION:
Make sure that the condensate can always be absorbed safe.
5.6 Automatic defrosting
During air drying, ice may form at the evaporator. The volume of ice depends on the
ambient conditions prevailing in the room to be dried. The air dryer is equipped with
an automatic hot-gas defroster. It ensures that, depending on the extent of ice
formation, the appliance will be defrosted automatically according to the following
principle:
A temperature sensor measures the condition existing in a critical area of the
evaporator.
It transmits the signal for defrosting to the DryLogic-electronic. The DryLogic
finds out if defrosting is necessary, and it will start defrost-mode on its own.
During defrosting the compressor works and the fan does not work.
When the ice is defrosted, the dehumidifier will start again with dehumidifying
6.Operation conditions
AD-condensation dryer AD 110 are suitable for the effort in water works, in
residential buildings, in swimming halls, in garages and storerooms. AD-
condensation dryer work problem-free at the temperature range of +3 to +32° C and
in the case of relative humidity from 40% to 95% r.h. .
The use in rooms with higher temperatures leads to disadvantages at the
compressor. The use in rooms with lower temperatures is ineffective and can lead
to icing.
Also the storage of the dehumidifier at inadmissible temperature conditions can lead
to damages / problems while immediate switch-on. Therefore, make possible short
time for adaptation for the device before switch-on
page 8 of 13
.