Initial Operation
When all of the mounting instructions have been carried out, a short visual test should be performed. The
smoke detector performs a short check of the function controls and self-monitoring when turned on
(activated). Wenn alle Montagevorkehrungen richtig erfüllt sind, sollte nochmals ein kurzer optischer Test
durchgeführt werden. Then the detectors switches to measuring operation and the operation display blinks
green.
Aerosol Test
A conventional test gas socket cannot be used here because of the self-monitoring and
-
manipulation recognition features of the smoke detector.
Only 3HS test gas sockets can be used with article number 8109.
-
Solo test gas sockets A3 are also suitable. The test socket with the article number 8109 is
-
required.
Function Test with Test Aerosol
1. Shake the test gas can.
2. Attach the 3HS test socket to the test gas tester. Make sure that the floor in the test socket is laid
out with non-reflecting material.
3. Connect the socket holder to the test gas tester.
4. Adjust the test rod to the necessary length.
5. Cover the smoke detector centrally with the 3HS test socket so that the LED´s and the measuring
window in the designated slots are visible. Spray the test aerosol into the test socket. (one or two
short sprays).
6. Wait at least 20 minutes and then spray again if necessary.
Notice
1. In order to obtain optimal results, shake the test gas can and make sure the surrounding
temperature does not exceed 15° C before testing.
2. If the display lights up yellow (Error) before turning red (alarm), this is not a malfunction. It shows
that the smoke detector has registered an error or manipulation.
3. If the smoke detector is in alarm mode (red display), the connecting voltage must be disrupted
briefly in order to turn off the alarm and return the device to normal operations (display blinking
green).