INSTALL FIRE BOLT
NOTE: Fire rated exit device with Less Bottom Rod (LBR) application must use a FIRE BOLT
3 ³/4" minimum
NOTES:
1. Prepare door edge as indicated for the Fire Bolt. Position Fire Bolt 4" to 6" above the finished floor
2. Drill 1" hole in the door edge as indicated and drill and tap for #8-32 machine screws
3. Install Fire Bolt on edge of door and fasten with supplied screws
4. Mark the plug hole on the frame in line with the fire bolt. Drill 1" diameter hole x 1³⁄4" deep on frame or
inactive door edge at same height as the Fire bolt and install strike hole plug
x 3³⁄8" (85 mm) Deep
4"-6"
13 / 16
Recess required if gap between door
and frame is less than 1/8" (3 mm).
#8-32 TAP
Auxiliary Fire Bolt
DXAFL
1" (25.4 mm) Hole
Strike
Hole
Plug