14. Connect wiring to new
compressor, be sure to
connect ground wire to the
body of compressor.
15. Using a nitrogen purge, braze
all joints.
16. Leak check and evaccuate to
at least 500 microns for 30
minutes.
17. Charge unit with R404A
refrigerant (7.9 oz on REF 4/5
and 10 oz on REF 5BB)
18. The replacement compressor
is taller and will not allow the
drain pan to be installed in the
original position (on REF4/5
models).
§ Adhere the supplied Velcro tape
to the bottom of the drain pan
(Fig. 11).
19. Reinsulate suction line with
supplied insulation and wire
tie in place using supplied wire
ties.
6
REF4/5 and REF5BB Compressor Retrofit
Fig. 10
Fig. 11