Atkinson Electronics A0217 Podręcznik - Strona 10

Przeglądaj online lub pobierz pdf Podręcznik dla Jednostka sterująca Atkinson Electronics A0217. Atkinson Electronics A0217 16 stron. Generator start control module

Atkinson Electronics A0217 Podręcznik
GSCM Adjustment Chart
Adjustment Formulas
0 - 60 Second/min/Vbat
0 – 120 (Sec)
15 – 75 Hz
Adjustment
0 - 60 Second Crank Delay
Maximum crank time
Load transfer delay
Load pre-off delay
Battery charge cut-in
Battery charge cut-out
Under speed shutdown
Over speed shutdown
Run/crank disconnect
30 day exercise runtime
* Both battery cut-in and cut-out must be at maximum for switched auto start.
** Both Over Hz and Under Hz must be set at zero to disable the Over or Under Hz Shutdown.
www.atkinsonelectronics.com
800.261.3602
TPV = (Desired Value ÷ 60) x 5
TPV = (Desired Sec ÷ 120) x 5
TPV = {(Desired Hz - 15) ÷ 60} x 5
0 Volts
5 second minimum
Will not energize starter
Ignition and load relays energize together
Ignition and load relays de-energize together
Ignores automatic battery charge function
Ignores automatic battery charge function
Ignores under speed shutdown condition**
Ignores over speed shutdown condition**
Uses 15Hz to disconnect starter
Deactivates 30 day exercise
Example: 11.5V Bat = 0.96V (TPV)
Factory Default Adjustments
Crank Delay
Maximum Crank
Load Transfer Delay
Load Pre-Off Delay
Battery Cut-In Volt
Battery Cut-Out Volt
Under Speed Shutdown
Over Speed Shutdown
Run/Crank Disconnect
30 Day Exercise Runtime @ deactivated - TPV = 0
10
55Hz = 3.33V (TPV)
65Hz = 4.17V (TPV)
@ 5s - TPV = 0.42V
@ 15s - TPV = 1.25V
@ 60s - TPV = 5V
@ 90s - TPV = 3.75V
@ 11.5V - TPV = 0.96V
@ 13.5V - TPV = 1.13V
@ deactivated - TPV = 0
@deactivated - TPV = 0
@ 30Hz - TPV = 1.25V
5 Volts
60 seconds
60 seconds
60 seconds
120 seconds
Switched auto start*
Switched auto start*
75Hz under speed shutdown
75Hz over speed shutdown
Over 60 Hz starter won't disconnect
1 hour 30 day run time
Circuit Board Division
Revised 09/18