Schedule (only visible if the unit has scheduling)
Day – Schedule day to be programmed.
Occ_Hour – Occupied hour to be programmed. This is the hour (in
24 hour format) that the unit will assume occupied status.
Occ_Minute – Occupied minute to be programmed. This is the
minute of the hour the unit will assume occupied status.
Unocc_Hour – Unoccupied hour to be programmed. This is the hour
(in 24 hour format) that the unit will assume unoccupied status.
Unocc_Minute – Unoccupied minute to be programmed. This is the
minute of the hour the unit will assume unoccupied status.
Config
Heat_Lockout – Heating mild weather stat setting. When the outside
or mixed air temperature is above this setting the burner will be
automatically disabled (only available if the unit has mild weather stat as an
option).
Cool_Lockout – Cooling mild weather stat setting. When the outside
or mixed air temperature is below this setting the cooling will be
automatically disabled (only available if the unit has cooling as an option).
Low_Temp_Alarm – If the unit discharges air below this temperature
set point for "Low Temp Time" minutes it will shut down and close the
isolation dampers (Only available if LTL is available).
Low_Temp_Time – The time delay (in minutes) for the "Low Temp
Alarm" (Only available if LTL is available).
Control_Type – Determines the type of control the unit will follow.
Enumerated "space/discharge".
Min_Discharge – The units minimum allowable discharge
temperature.
Max_Discharge – The units maximum allowable discharge
temperature.
Cycle_Occupied – Determines if the unit will cycle on/off to space
temperature when in occupied status. Enumerated "yes/no".