Man_Econ_Speed – Manual Economizer setting for "two speed" or
"two position" economizer operation (only available if the unit has two
position or two speed as an option). Choices are "LOW" and "HIGH". These
values are set in the "CONFIG" menu.
Burner_Reset – Burner reset command for use during a burner
lockout alarm. This is an "on/_on_" toggle selectable via the "up arrow"
button.

Status

Space_Temp – Current space temperature at the User Interface (or
remote space temperature sensor if equipped).
OA_Temp – Current outside air temperature.
RA_Temp – Current return air temperature (only if the unit has return
air as an option).
DA_Temp – Current discharge air temperature.
Cool_Coil_Temp - Current cooling coil exit temperature (only if the
unit is equipped with cooling).
Bldg_Pressure – Current building pressure (only available if the unit
has building pressure as an option).
Econ_Command – Current economizer command issued to the
dampers or supply fan VFD (only available if the unit has an economizer
option).
Heat_Command – Current command (0% - 100%) issued to the
burner for heat.
Cool_Command - Current command (0% - 100%) issued to the
cooling system (only if the unit is equipped with cooling).
Active_Stages - Current number of active cooling stages (only if the
unit is equipped with cooling).